15
INSTALLATION
(3) Obstacles on right and left side of single installation.
(a) There is no obstacle in the upper side. Unit: mm
(b) There are obstacles in the upper side. Unit: mm
(4) Multi-row and multiple installations. Unit: mm
Note:
If L is larger than H, mount the units on a base so that H is greater or equal to L. Be sure to seal up every surface of the base. If the
base allows the airow to go, it may cause a short-circuit.
L A (mm) B (mm)
0 < L ≤ 1/2H 600 or more 300 or more
1/2H < L ≤ H 1400 or more 350 or more