I
Temperature DB: Dry Bulb, WB: Wet Bulb
Maximum Minimum
Cooling
Operation
Indoor 32°C DB/23°C WB 21°C DB/15°C WB
Outdoor Stable 48°C DB Interval 48~52°C DB -5°C DB *
Heating
Operation
Indoor 27°C DB 15°C DB
Outdoor 24°C DB/15°C WB Stable -15°C WB Interval -20~-15°C WB
Note:
*: When RAS-7.0~12HNBRMQ1 outdoor units are connected with the RCIM-0.8FSN4 or RCD-0.8~1.0FSN3 or RCS-0.8~1.0FSN, if only
one of these indoor unit is operating in cooling mode, the minimum outdoor temperature is limited to 5°C DB.
IMPORTANT NOTICE
The company pursues a policy of continuous improvement in design and performance of products. The
right is therefore reserved to vary specications without notice.
The company cannot anticipate every possible circumstance that might involve a potential hazard.
This heat pump air conditioner is designed for standard air conditioning only. Do not use this heat pump
air conditioner for other purposes such as drying clothes, refrigerating foods or for any other cooling or
heating process.
Do not install the unit in the following places. It may cause a re, deformation, corrosion or failure:
* Places where oil (including machinery oil).
* Places where a lot of sulde gas drifts such as in hot spring.
* Places where inammable gas may generate or ow.
* Places where strong salty wind blows or with an atmosphere of acidity or alkalinity such as coastal
regions.
Do not install the unit in the place where silicon gas drifts. If the silicon gas attaches to the surface of
heat exchanger, the n surface repels water. As a result, drain water splashes outside the drain pan and
splashed water runs into electrical box. In the end, water leakage or electrical devices failure may occur.
Pay attention to the following points when the unit is installed in a hospital or other facilities where
electromagnetic wave generates from medical equipment.
* Do not install the unit in the place where the electromagnetic wave is directly radiated to the electrical
box, wired controller cable or switch.
* Install the unit at least 3 meters away from electromagnetic wave such as a radio.
Do not install the unit in the place where the breeze directly blows to the animals and plants. It could
adversely a󰀨ect the animals and plants.
The installation and service engineering should be in accordance with the local laws and regulations.
If you have any questions, contact your distributor or dealer.
The installation of this air conditioner can only be carried out by dealers or specialists. If the user installs
the air conditioner by himself, it may cause leakage, electric shock or re.
This manual gives a common description and information for this heat pump air conditioner and also for
other models.
To protect the environment, do not discard the product at will, the company can provide recycling services
as per the relevant provisions of the country, and provide replaceable components as per national
standards.
No part of this manual may be reproduced without written permission.
It is assumed that this heat pump air conditioner will be operated and serviced by English speaking
people. If this is not the case, the customer should be added safety, caution and operating signs in the
native language.
This heat pump air conditioner has been designed for the following temperatures. Operate the heat pump
air conditioner within this range.

Table of Contents

Other manuals for Hitachi RAS-8.0HNBRMQ1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RAS-8.0HNBRMQ1 and is the answer not in the manual?

Hitachi RAS-8.0HNBRMQ1 Specifications

General IconGeneral
BrandHitachi
ModelRAS-8.0HNBRMQ1
CategoryAir Conditioner
LanguageEnglish

Related product manuals