83
Alarm
Code
13
Abnormality of Thermistor for Liquid Refrigerant Pipe Temperature at Indoor Unit Heat
Exchanger (Freeze Protection Thermistor)
●
The alarm code is ashed on the 7-segment display of the outdoor unit.
●
The alarm code is displayed on the wired controller of the indoor unit.
★
This alarm code is displayed when a short circuit (0.24kΩ or less) or disconnection (840kΩ or more) of
the thermistor is detected during a heating or cooling operation. The operation automatically restarts when
the malfunction is removed.
TROUBLESHOOTING