Item
7-segment display
Details
SEG2 SEG1
25
Compressor MC2 accumulated
operating time
cU 20
Unit: hour (Indication x 10 hours)
Only 14 HP to 18 HP
The accumulated
operating time can be reset. *2)
26 Cause of the Inverter stoppage
 10
Refer to the "Inverter stoppage cause table". *3)
27 Cause for fan controller stoppage
F 10
Refer to the "Cause for fan controller stoppage"
*4)
*1) The indicated current is a reduced value. Use a clamp meter for the current precise value.
*2) To
reset the accumulated operating time, press "PSW1 and PSW3" for five seconds while the accumulated data is
displayed.
(Example)
SEG2 SEG1
NOTE: The outdoor unit No. is indicated on the one digit of “SEG1”
*3) Cause of the Inverter stoppage: display digits indication
 10
1: compressor No.
0: outdoor unit No.
*4) Cause for fan controller stoppage display digits indication
F 10
1: fan controller No.
0: outdoor unit No.
Capacity table for the outdoor units.
Indication Capacity (kW) Horsepower (HP)
64 22.4 8.0
80 28.0 10.0
96 33.5 12.0
112 40.0 14.0
128 45.0 16.0
144 50.0 18.0
N O T E
In the
case of unit combinations, the outdoor unit capacity indication is the total capacity of the constitution units.
Example:
In the case of unit RAS-54FSXN:
RAS-54FSXN = RAS-18FSXN x 3
144 x 3 = 432
Indication "432" will be displayed.
(D) Indoor unit information
This information is indicated on unit A (main unit) only.
Select the indoor unit number for information indication.
8 Troubleshooting
252
SMGB0065 rev. 1 - 12/2010