Press PSW4 (▼) to move forward or PSW2 (▲) to move back.
Select the indoor unit number for indication.
Press PSW3 (►) for more detailed information on the unit number selected.
Unit no. Indication
No. 0
d00
No. 1
d01
No. 63
…d63
Press PSW4 (▼) to move forward or PSW2 (▲) go back.
This information will be alternatively indicated as “Item” “Details”.
Press PSW5 (◄) to return to the indoor unit No. selection.
Indication details:
Item
7-segment display
Details
SEG2 SEG1
1 Capacity of the indoor unit
CA 00
Unit capacity indication.
Refer to the "Capacity table for the indoor units".
2 Opening of the expansion valve
E 00
Unit: %
3
Heat exchanger liquid pipe
temperature
L 00
Unit: °C
4
Heat exchanger gas pipe
temperature
G 00
Unit: °C
5 Air inlet temperature
 00
Unit: °C
6 Air outlet temperature
o 00
Unit: °C
7 Unit stoppage cause code
d1 00
Indoor unit stoppage cause code indication.
Refer to the "Indoor unit stoppage cause table".
NOTE: The indoor unit No. is indicated on “SEG1”
SEG2 SEG1
(Example)
Capacity table for the indoor units.
Indication
Capacity
(kW)
Horsepower
(HP)
Indication
Capacity
kW)
Horsepower
(HP)
Indication
Capacity
(kW)
Horsepower
(HP)
6 2.2 0.8 14 5.6 2.0 40 14.0 5.0
8 2.8 1.0 16 6.7 2.3 48 16.0 6.0
10 3.8 1.3 18 7.1 2.5 64 22.4 8.0
11 4.0 1.5 22 8.0 3.0 80 28.0 10.0
13 5.2 1.8 32 11.2 4.0
(E) Cause for alarm code information
This information is indicated in unit A (main unit) only.
Press PSW4 (▼) to move forward or PSW2 (▲) to go back.
This information will be indicated alternating as “Item” “Details”.
8 Troubleshooting
253