Press PSW4 (▼) to move forward or PSW2 (▲) to move back.
Select the indoor unit number for indication.
Press PSW3 (►) for more detailed information on the unit number selected.
Unit no. Indication
No. 0
d00
No. 1
d01
↓ ↓
No. 63
…d63
Press PSW4 (▼) to move forward or PSW2 (▲) go back.
This information will be alternatively indicated as “Item” → “Details”.
Press PSW5 (◄) to return to the indoor unit No. selection.
Indication details:
Item
7-segment display
Details
SEG2 SEG1
1 Capacity of the indoor unit
CA 00
Unit capacity indication.
Refer to the "Capacity table for the indoor units".
2 Opening of the expansion valve
E 00
Unit: %
3
Heat exchanger liquid pipe
temperature
L 00
Unit: °C
4
Heat exchanger gas pipe
temperature
G 00
Unit: °C
5 Air inlet temperature
00
Unit: °C
6 Air outlet temperature
o 00
Unit: °C
7 Unit stoppage cause code
d1 00
Indoor unit stoppage cause code indication.
Refer to the "Indoor unit stoppage cause table".
NOTE: The indoor unit No. is indicated on “SEG1”
SEG2 SEG1
(Example)
• Capacity table for the indoor units.
Indication
Capacity
(kW)
Horsepower
(HP)
Indication
Capacity
kW)
Horsepower
(HP)
Indication
Capacity
(kW)
Horsepower
(HP)
6 2.2 0.8 14 5.6 2.0 40 14.0 5.0
8 2.8 1.0 16 6.7 2.3 48 16.0 6.0
10 3.8 1.3 18 7.1 2.5 64 22.4 8.0
11 4.0 1.5 22 8.0 3.0 80 28.0 10.0
13 5.2 1.8 32 11.2 4.0
(E) Cause for alarm code information
This information is indicated in unit A (main unit) only.
Press PSW4 (▼) to move forward or PSW2 (▲) to go back.
This information will be indicated alternating as “Item” → “Details”.
8 Troubleshooting
253
SMGB0065 rev. 1 - 12/2010
8