10 
A10762300A-rev.1
4.2 InitialCheck
Fig.4.1SpacearoundIndoorUnit
 
•
 Considertheairdistributionfromtheindoorunit
tothespaceoftheroom,andselectasuitable
locationsothatuniformairtemperatureinthe
roomcanbeobtained.
 
•
 Avoidobstaclessuchaselectriclight,partition
whichmayhampertheairinletortheairoutlet
ow.
 
•
 Checktoensurethattheceilinghasasucient
strengthtohangtheindoorunit.
 •
 Donotinstalltheindoorunitinamachineryshop
orkitchenwherevaporfromoiloritsmistows
totheindoorunit. 
Anoilwilldepositontheheatexchanger,
therebyreducingtheindoorunitperformance
andtheplasticpartsmaydeform,andinthe
worstcase,breakduetosplashoilatoperation.
 
•
 Avoidtheinstallationplacewheretheindoorunit
maycontacthighhumidity.
 
•
 Thewarmedairmaystayatthehighceiling
spaceduringtheheatingoperation.Thus,the
parallelinstallingofacirculatorisrecommended.
 
•
 Theindoorunitcanbeinstalledupto3.5meters
(for1.5to3HP)and4.3meters(for4to6HP)
fromtheoorlevel.
 •
 Avoidinstallingtheairconditioningwherethe
directairowblowsfromtheairoutlettothe
temperaturedetectingdevicessuchanalarm
deviceoracontroldevice.Itmaycauseafailure
ofanalarmdeviceoracontroldevice.
(Total Refrigerant Quantity per one Outdoor Unit)
Volume of the room where this
Indoor Unit is installed.
( )
≤
0.3kg/m
3
●
Check to ensure that the number of below 
is within 0.3kg/m
3
.  Otherwise it may cause 
danger situation if the refrigerant in the 
Outdoor Unit leaks into the room where this 
Indoor Unit is installed.
  In detail, refer to the Installation Manual for 
outdoor unit.
●
Make sure that a refrigerant leak test has 
been performed. Refrigerant (Fluorocarbon 
or Diuoromethane) for this unit is non-
toxic, and odorless. If the refrigerant  should 
somehow escape and come into contact with 
ame, toxic gas will form. This gas is heavier 
than air and will settle near oor areas and 
spread where it can cause suocation to 
those nearby. In addition, diuoromethane is 
ammable and can cause re.
 
•
 Installtheindoorunitwithaproperclearance
arounditforoperationandmaintenanceworking
space,asshowninFig.4.1.
 
•
 Donotinstallammablepartsintheservice
spacefortheindoorunit.
 
•
  Installtheindoorunithigherthan2.4meters
fromtheoorlevel.
  NOTE: 
Ifthereisacorniceontheceiling,measurethedimensionfromthefrontorundersurface.
<ForSingleInstallation>
<ForParallelInstallation>
Min. 40
Min.
300
Min.
300
Min. 40
Minimum service space to
tighten the suspension bolt
Min.
300
Min. 400
Min.
500
Min.
2500
Min. 8
Minimum service space
for auto louver motor