A10762300A-rev.1 
39
(4) CapacityCodeSetting(DSW3) 
Nosettingisrequired,duetosettingbefore
shipment.Thisswitchisutilizedforsetting
thecapacitycodewhichcorrespondstothe
HorsePoweroftheindoorunit.
(5) UnitModelCodeSetting(DSW4) 
Nosettingisrequired. 
Itisforsettingthemodelcode 
oftheindoorunit.
(6) RefrigerantCycleNo.Setting 
(RSW1&DSW5) 
Settingisrequired.Settingpositionsbefore
shipmentareallOFF.
● Inthecaseofapplyinghigh
voltagetotheterminal1and
2ofTB2,thefuse(0.5A)on
thePCBiscut. 
Insuchacase,rstly
reconnectthewirings
correctlytoTB2,andthen
turnonNo.1pin.
7.7 FunctionSelectionbyWiredController
Eachfunctioncanbeselectedfromthewired
controller(PC-ARF1).
Thedetailshouldbereferredto“Installation&
MaintenanceManual”forthewiredcontrollerand
“TechnicalCatalog”.
(1) CirculatorFunctionatHeatingThermo-OFF 
Thisfunctionmaintainsthefanoperationby
thesetairowvolumeattheheatingTermo-
OFF.Itisforimprovementoftemperature
distributionathighheightceilingsite.
(2) Cooling/HeatingAutoChangeoverDual
SetpointControl
 Incasedualsetpointisselectedinautomatic
heating/coolingoperation,duringautomode
bothcoolingsetpointandheatingsetpoint
canbeselected.
(3) SetbackOperation
 Setbackoperationismainlytosustain
acomfortroomairtemperaturewhile
occupantsareoutoftheroom.Ifthe
setbackoperationisenabled,thesetpointis
adjustedforsetback.
TurnOFFallthepowersupplyoftheindoorunit
andtheoutdoorunitbeforeDipSwitchsetting. 
Ifnot,thesettingisinvalid.
(7) FuseRecover(DSW7)
● FactorySetting
(8) OptionalFunctionSetting(DSW9)
● FactorySetting
1 2 3 4
Setting
Position
2.0 2.5Horsepower
Setting
Position
3.0
4.0 5.0 6.0Horsepower
1.5
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1234
NOTE
●  The “
n
”markindicatespositionofdipswitches. 
Figuresshowsettingbeforeshipment.
●  Whentheunitnumberandtherefrigerantcycle
areset,recordtheunitnumberandrefrigerant
cycletofacilitatemaintenanceandservicing
activitiesthereafter.
3
4
1
0
8
9
2
5
6
7
3
4
1
0
8
9
2
5
6
7
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5 (Tens Digit)
Refrigerant Cycle No. Setting
RSW1 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.5 Cycle
DSW5
RSW1
Set All Pins OFF
Set at "5"
Before shipment, DSW5 and RSW1 are set at "0".
(a) for Units Supporting H-LINK II
     The ref. cycle Nos. can be set for Max. 64 cycles.
     (No. 0~63)
(b) for Units Supporting H-LINK
     The ref. cycle Nos. can be set for Max. 16 cycles.
     (No. 0~15)