7.3 PositionofElectricalWiringConnection
● Tightly secure wirings to the terminal
block according to the specied torque. If
tightening the terminals is not completed,
heat generation, an electric shock or a re
will occur at the terminal connection.
● Make sure that the wires are securely xed
in order not to apply an external force to the
terminal connection of the wirings. If xing is
not completed, heat generation or a re will
occur.
• Theelectricalwiringconnectionfortheindoor
unitisshownintheitem7.2.2.
• Theconnectionattheterminalblockforthe
indoorunitisshowninthegurebelow.Check
theoutdoorunitforthecombinationbeforethe
wiringwork.Thescrewsattheterminalblock
shouldbeperformedaccordingtothetightening
torqueasshowninthetablebelow.
(1) Connectthecablefortheoptionalwired
controllerortheoptionalextensioncable
totheterminalsinsidetheelectricalbox
throughtheconnectingholeinthecabinet.
(2) Connectthepowersupplyandtheearth
wirestotheterminalsintheelectricalbox.
(3) Connectthewiresbetweentheindoorunit
andtheoutdoorunittotheterminalsinthe
electricalbox.
(4) Connectcablescorrectlytomatchthe
terminalNo.andthemarkband.
(5) Connectthetransitionwiresbetweenindoor
unitsconnectedtothesameoutdoorunit.
(6) Donotconnectthemainpowersource
cablestothecontrolline(TerminalsA,B,
1and2ofTB2).Ifconnected,theprinted
circuitboard(PCB)willbebroken.
(7) Tightlyclampthewiresusingthecordclamp
insidetheelectricalbox.
(8) Standardcompliancewheninstallingtheunit
inAustralia.
(a) Connectthebothendsofshieldedtwist
paircable(controllercableandcontrol
cable)totheearthasshownbellow.
TighteningTorqueforTerminals
TighteningTorque
M4 1.0 - 1.3 (N-m)
TerminalBlockfor
PowerSourceCable
TB1(black)
TerminalBlockfor
ControlCable
TB2(white)
● Donotconnectthemainpowersourcecablesto
thecontrolline(TerminalsA,B,1and2ofTB2).
Ifconnected,theprintedcircuitboard(PCB)will
bebroken.
● Payattentiontofollowingswhenwiresare
connectedtoterminalblock.
(A) Attachaninsulationtapeorasleevetoeach
terminal.
(B) Maintainthedistancebetweentheelectrical
boxandtheterminalstopreventashort
circuit.
(C) Maintainthedistancebetweentheterminals.
(b) Alockableisolatorshallbemounted
adjacenttobutnotontheunitandwill
disconnectallactiveconductorstotheunit
fromthesupplycircuit.
-
S/NR/L1
AB
12
Shielded Twist Pair Cable
Shield
EarthEarth
Wires
(A)
(B)
(C)
Screw