7.4 TransitionWiringforWiredController
Inthetwin,triple,andquadcombinationofindoorunits,thetransitionwiringforthewiredcontrollerisnot
required.However,whenconnectingindoorunitswithouttransitionwiringforwiredcontroller,thefollowings
arelimited.
(2)ThefollowingconnectionisNOTavailable.
(a) ConnectionbetweenMainUnitswithoutTransitionWiring 
Whentheindoorunitsinmultiplerefrigerantcyclesarecontrolledbyonewiredcontroller,allthe
indoorunitsarerequiredtobeconnectedwiththetransitionwirings.
(b) ConnectionbetweenMainUnitwithoutTransitionWiringandUnitwithTransitionWiring 
Whentheindoorunitsinmultiplerefrigerantcyclesarecontrolledbyonewiredcontroller,allthe
indoorunitsarerequiredtobeconnectedwiththetransitionwirings.
(1) Thefollowingfunctionsareavailabletosetonlyto
themainunitwiththewiredcontrollerPC-ARF1.
 *“RemoteON/OFFfunction,1and2" 
*“PowersupplyON/OFFfunction,1and2" 
*“Prohibitingoperationbywiredcontroller”
Incorrect Correct
Incorrect Correct
(c) ConnectingWiredControllertoSubunitwithoutTransitionWiring 
Whentheindoorunitsarecontrolledby2wiredcontrollers,thesubwiredcontrollershallbe
connectedtothemainunit.
Incorrect Correct
Transition wiring is unnecessary.