14 
A10762300A-rev.1
5.  Refrigerant Piping Work
(3) Prepareeld-suppliedcopperpipes.
(4) Selectcleancopperpipes.Makesurethereisnodustandmoistureinside.
(5) TherefrigerantlubricatingoilusedintheseunitsisPolyvinylether(PVE),achemicallystable,resilient,
syntheticlubricantthat,whencombinedwithrefrigerantR410AorrefrigerantR32,maintainsits
compatibility,lubricity,andviscosityoverextendedperiodsoftimeandisimpervioustoheat,oxidation,
moistureabsorptionandbreakdownaslongasitremainsinasealedsystem.Itschemicalproperties
willremainintactonlysolongasmoistureisnotintroducedintothesystem.
Thegaseouselement,PVEisamoisturemagnetthat,onceexposedtoopenairandcan
quicklybecomesaturatedwithmoisture,loseitslubricity,andbecomeuseless.Minimize
exposuretotheopenair,overthesummermonths,andinsouthernortropicalclimates.
(6) Useapipecuttertoavoidagrindswarfgenerationforthepipecuttingwork.(Donotuseasawora
grindstonetocutpipes.)Blowtheinsideofthepipeswithnitrogenordryair,toremoveanydustor
foreignmaterialsbeforeconnectingpipes.
5.1 PipingMaterials
(1) Thetoleranceofrefrigerantpipinglengthdiersdependingonthecombinationwiththeoutdoorunit.
Thedetailsshallbereferredto“Installation&MaintenanceManual”oftheoutdoorunit.
(2) Selectthepipingsizefromthefollowingtable.
mm(in.)
Model GasPiping LiquidPiping
RPC-1.5FSR
RPC-2.0FSR
f
12.7 (1/2)
f
6.35 (1/4)
RPC-2.5FSR
RPC-3.0FSR
RPC-4.0FSR
RPC-5.0FSR
RPC-6.0FSR
f
15.88 (5/8)
f
9.52 (3/8)
Fortherefrigerantpipingwork,vacuumpumpandrefrigerantcharge,thedetailsshallbereferredto
“Installation&MaintenanceManual”oftheoutdoorunit.
This machine uses refrigerant R410A or refrigerant R32. 
The type of enclosed refrigerant is described in the specication nameplate and caution nameplate 
attached to the outdoor unit. When installing, repairing, or relocating, do not mix substances other 
than the refrigerant described on the specication nameplate or caution nameplate attached to 
the outdoor unit. Also, do not mix refrigerant R410A and refrigerant R32. Entering non-designated 
refrigerants, air, oxygen, ammable substances such as propane or alcohol may cause explosion, 
re or injury.
When installing pipe through
the wall, secure a cap at the
end of the pipe.
Correct
CorrectIncorrect Incorrect
Correct Incorrect
HoleHole
Attach a cap
or vinyl tape.
Attach a cap
or vinyl tape.
Attach a cap
or vinyl bag with
Do not place the pipe
directly on the ground.
Rain water
can enter.