A10762300A-rev.1
45
9. Safety and Control Device Setting
IndoorUnit
Model
RPC-1.5FSR,RPC-2.0FSR,
RPC-2.5FSR,RPC-3.0FSR,
RPC-4.0FSR,RPC-5.0FSR,
RPC-6.0FSR
ForEvaporatorFanMotor
Thermostat Cut-Out
o
C 100
+15
-10
Cut-In
o
C 95
+15
-10
ForControlCircuit
Fuse
Capacity A 5
FreezeProtection
Thermostat Cut-Out
o
C 0
Cut-In
o
C 11
Thermostat
Di󰀨erential
o
C 2
Alltheinstallationworkoftheairconditioningiscompleted.
Deliveranddescribetokeepthis“Installation&MaintenanceManual”toauser.
RefrigerantLeakCheck
Conductaperiodicrefrigerantleakchecktomaintainproductperformanceandsecurestorageofrefrigerant.
Aftercompletinginstallation,recordthefollowingresultsintothis"InstallationandMaintenanceManual":
1. Resultsofatestforair-tightintegrity
2. Totalrefrigerantchargevolumedispensed(includingatrimchargeaddedfollowingtheinstallation)
3. Resultoftherefrigerantleakcheck
Thenhanditovertousersandaskthemtoretainforreference.
Allperiodicserviceandmaintenanceproceduresmustbeconductedonlybyauthorizedandtrainedpersonnel.
Alltheinstallationworkoftheairconditioningiscompleted.
Handoverthisinformationtothebuildingownerandrequesttomaintainalltheequipmentmanuals
andwarranty.