7.4.2 CautionsforMotionSensorKit(SOR-NEP)
(1) Themotionsensorcanbeconnectedupto16indoorunitsbyonewiredcontroller(PC-ARF1).The
motionsensorwillbeactivatedevenifitisinstalledwithoutmotionsensor.
(2) Whenthemultipleindoorunitswithmotionsensorarecontrolledbyonewiredcontroller(PC-ARF1),
thetransitionwiringforwiredcontrollerisrequiredtoalltheindoorunits.Ifnot,theindoorunitswith
motionsensorwillnotbeactivated.
(3) Inthecasethat2wiredcontrollersareconnected,themotionsensorcanbesetononlythemain
wiredcontroller.Thesubwiredcontrollerisfortheindicationonly.
Wired
Controller
Transition Wiring for Wired Controller
with Motion
Sensor Kit
with Motion
Sensor Kit
with Motion
Sensor Kit
with Motion
Sensor Kit
Wired Controller
(PC-ARF1)
Main: Setting is available.
Wired Controller
(PC-ARF1)
Sub: Setting is NOT available.
with Motion
Sensor Kit
with Motion
Sensor Kit
(4) Theoutdoorunitmodelcanbecontrolledbymeansofamotionsensorkit.
(5) ThewiredcontrollerPC-ARF1mustbeutilized.Othersarenotavailabletosetthemotionsensor.
(6) ThemotionsensorfunctionisNOTcorrespondingtheindoorunitwithoutwiredcontroller.
(7) Themotionsensorcannotbesetfromthecentralizedstations.
(8) Themotionsensorcannotbeusedwhenitisconnectedtothesamewiredcontrollerwithanindoor
unitinotherrefrigerantcyclewhichissetasthesimultaneousoperation.
(9) Theroomthermostatfunctionisnotavailable.