62 Frequency lower limit setting A6 F-26 LIMIT L 0.0Hz A062
A value for the second motor can be set independently by
A262 in the case of the SJ300.
63 Frequency upper limit setting A5 LOMIT H 0.0Hz A061 0.00
A value for the second motor can be set independently by
A261 in the case of the SJ300.
64 Jump frequency setting 1 A7 JUMP F1 0.0Hz A063 0.00
65 Jump frequency setting 2 A8 JUMP F2 0.0Hz A065 0.00
66 Jump frequency setting 3 A9 JUMP F3 0.0Hz A067 0.00
67 Jump frequency width setting - JUMP W 0.5Hz Note 0.50 Note: Jump frequency width setting: A064, A066, and A068
68 Allowable instantaneous power failure time - F-22 IPS TIME 1.0s b002 1.0
69 Retry wait time before motor restart - IPS WAIT 1.0s b003 1.0
70
Selection of automatic restart mode after
instantaneous power failure
A34 IPS POWR ALM b001 00
71 Voltage trip enable during stop - IPS TRIP OFF b004 00
72 Maximum frequency selection A64 F-30 F-MAX-L 120Hz - - No need to set in the case of the SJ300
73 Software lock mode selection - F-25 S-LOCK MD1 b031 01
74 STOP key enable - F-28 STOP-SW ON b087 00
75 Rotational direction restriction - F/R SWF-29 FRE b035 00
76 Reverse RUN protection enable - F/R PREEV OFF b046 00
77 Analog input selection A48 F-31 IN ANA 10V Note - Note: Please adjust with analog input setting functions
78 Analog input active range start frequency A26 IN EXS 0.0Hz Note 0.00 Note: (SJ300) O: A011, OI: A101, O2: A111
79 Analog input active range end frequency A27 IN EXE 0.0Hz Note 0.00 Note: (SJ300) O: A012, OI: A102, O2: A112
80 Analog input active range start voltage/current - IN EX%S 0% Note
0(O), 20(OI),
-100(O2)
Note: (SJ300) O: A013, OI: A103, O2: A113
81 Analog input active range end voltage/current - IN EX%E 100% Note 100 Note: (SJ300) O: A014, OI: A104, O2: A114
82 Analog input start frequency enable - IN LEVEL 0Hz Note 01(0Hz) Note: (SJ300) O: A015, OI: A105
83 External frequency filter time constant A11 IN F-SAMP 8 A016 8
84 Frequency arrival signal output method A49 F-32 ARV PTN CST Note -
Note: Selection from FA1 to FA5 at an intelligent output
terminal
85 Frequency arrival setting for acceleration A39 ARV ACC 0.0Hz C042(045) 0.00
86 Frequency arrival setting for deceleration A40 ARV DEC 0.0Hz C043(046) 0.00
87 Over-torque (forward) level setting - F-33 OV-TRQ V 100% C055/C056 100
Note: Forward-driving/reverse-regenerating can be set
independently in the case of the SJ300.
88 Over-torque (reverse) level setting - OV-TRQ R 100% C057/C058 100
Note: Reverse-driving/forward-regenerating can be set
independently in the case of the SJ300.
89 Intelligent input terminal 1 function C0 IN-TM 1F-34 RS C001 18(RS)
90 Intelligent input terminal 2 function C1 IN-TM 2 AT C002 16(AT)
91 Intelligent input terminal 3 function C2 IN-TM 3 JG C003 06(JG)
92 Intelligent input terminal 4 function C3 IN-TM 4 FRS C004 11(FRS)
93 Intelligent input terminal 5 function C4 IN-TM 5 CH1 C005 09(2CH)
94 Intelligent input terminal 6 function C5 IN-TM 6 CF2 C006
03(CF2)(CE
ver.)/13(USP)(UL
ver.)
95 Intelligent input terminal 7 function C6 IN-TM 7 CF1 C007 02(CF1)
96 Intelligent input terminal 8 function C7 IN-TM 8 REV C008 01(RV)
J300 SJ300No.
Name
Function code Default Function Default setting
Remarks