Component
Component
model number
Power
consumption
(VA) Heat output
Airflow
(m
3
/min)
Weight
(kg)
SCM 375GB
NVMe Drive
DKC-
F910I-375YVM
20 19 - 0.19
1. Maximum values when all fans rotate at the maximum speed.
Electrical specifications
The Hitachi Virtual Storage Platform 5000 series storage system Power Distribution Units
(PDUs) support single-phase AC power.
The Hitachi rack comes with either two, four, or six PDUs, depending on the PDU model
selected. The PDUs are installed vertically in the rack.
■
If two PDUs are selected, one will be installed on the left side of the rack and the
other will be installed on the right side.
■
If four PDUs are selected, the PDUs will be half-length and mounted vertically, one
above the other, with two on the left side of the rack and two on the right side.
■
If six PDUs are selected, the PDUs will be 1/3-length and mounted vertically, one
above the other, with three on the left side of the rack and two on the right side.
Note: The current and power specications of the storage system in the
following tables were measured in a controlled environment. To calculate the
power and current draw, and heat output of a specic system, see Physical
specications (on page 57) or use the weight and power calculator at the
following URL:https://www.hitachivantara.com/ext/weight-and-power-
calculator.html .
If you need assistance using this tool, contact Hitachi Vantara Support
athttps://support.hitachivantara.com/en/contact-support.html .
Item
Input
Power
Inrush Current
(Rating)
1
Leakage
Current
Inrush Current
When one
PS is
operating
When two
PSs are
operating 1st (0-p) 2nd (0-p)
1st (0-p)
Time
(-25%)
Node
power
supply
Single
phase,
AC200V to
AC240V
7.2 A 3.6 A 1.75 mA 30 A 30 A 25 ms
Electrical specications
Chapter 3: Specications
Hitachi Virtual Storage Platform 5000 Series Hardware Guide 63