Specifications
A–3
Hitachi VSP User and Reference Guide
Table A-2 VSP electrical specifications. single phase current
Item Unit Specification
Power requirements,
system operating
.
Maximum total power
consumption for a two
module system during
normal operation is 98
amps.
-
Maximum total power
consumption for a fully
configured two module
system (2048 disk drives)
with all drives in write
mode is 112 amps.
AC, single phase
2 pole + ground
200 V to 240 V, +6% -8%
50 Hz ±3 Hz, 60 Hz ± 2 Hz
Drive chassis
(240 HDD)
4.3KVA (2.5" SAS)
5.7KVA (3.5” SATA)
Maximum 41.4 KVA
Controller chassis power
supply
Input Current 7.18 A
Steady Current 3.59 A
Leakage Current 0.28 mA
Inrush current 1st (0-p) 20 A
2nd (0-p) 15A
1st (0-p) Time
(-25%: 80 ms
Drive chassis
power supply
Input Current 6.52 A
Steady Current 3.26A
Leakage Current 0.28 mA
Inrush current 1st (0-p) 20 A
2nd (0-p) 15A
1st (0-p) Time
(-25%: 80 ms
Power consumption,
system in standby
-
Maximum total power
consumption for a two
module system in standby
mode is 75 amps.
Control chassis 0.79 KVA
Drive chassis 1.34 KVA
Rack with one control
chassis and two drive
chassis
3.47 KVA
Rack with three drive
chassis
4.02 KVA
Single module (3 rack
system)
11.51 KVA
Dual module (6 rack
system)
23.02 KVA / 75 A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi Virtual Storage Platform and is the answer not in the manual?

Hitachi Virtual Storage Platform Specifications

General IconGeneral
Drive TypesSSD, SAS
RAID SupportRAID 1, RAID 5, RAID 6, RAID 10
ConnectivityFibre Channel, iSCSI, FCoE
Form FactorRack-mounted
CategoryEnterprise Storage System
Data ReductionDeduplication and Compression (capabilities vary by model and software version)
Operating System CompatibilityWindows, Linux, UNIX, VMware
High AvailabilityRedundant components
ScalabilityScale-up and scale-out
ModelVirtual Storage Platform (VSP)

Related product manuals