EasyManuals Logo

Hitachi Virtual Storage Platform User Manual

Hitachi Virtual Storage Platform
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
Specifications
A–7
Hitachi VSP User and Reference Guide
Equipment noise
The acoustic emission values [loudness in dB (A)] for the VSP storage
system storage system are:
Front/rear = 65 dB (A)
Both sides = 65 dB (A)
Heat output and air flow
The following table lists the heat output and air flow requirements for the
VSP storage system components.
Both the control chassis and the disk chassis contain front and rear fans to
circulate air through the chassis from front to back. Air flows in through the
front bezel to the rear of the component and exits through the perforations
in the rear door. Either the front fans or the rear fans can cool the chassis
by themselves. The racks do not contain fans. Airflow is from front to back.
Table A-7 VSP Heat, Power, and airflow
Model Number
Heat Output
(kW)
Power
Consumption
(kVA)
Air Flow
cubic ft / cubic
meters/min)
DKC710I-CBX
0.475
1
0.500
1
247.2 / 7.0
DKC-F710I-SBX
0.570
1
0.600
1
317.8 / 9.0
DKC-F710I-UBX
0.570
1
0.600
1
317.8 / 9.0
DKC-F710I-SVP 0.052 0.055 -
DKC-F710I-HUB 0.010 0.010 -
DKC-F710I-16MFS 0.118 0.124 -
DKC-F710I-16MFL 0.118 0.124 -
DKC-F710I-8UFC 0.072 0.076 -
DKC-F710I-16UFC 0.072 0.076 -
DKC-F710I-16MUS 0.118 0.124 -
DKC-F710I-16MUL 0.118 0.124 -
DKC-F710I-SCA 0.080 0.084 -
DKC-F710I-CPC 0.068 0.072 -
DKC-F710I-C16G 0.019 0.020 -
DKC-F710I-BM64 0.005
0.005
2
-
DKC-F710I-MP 0.190 0.200 -
DKC-F710I-ESW 0.070 0.074 -
DKC-F710I-146KCM 0.013 0.014 -
DKC-F710I-300JCM 0.013 0.014 -
DKC-F710I-500HCM 0.013 0.014 -
DKC-F710I-600JCM 0.013 0.014 -
DKC-F710I-2R0H2M 0.020 0.021 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi Virtual Storage Platform and is the answer not in the manual?

Hitachi Virtual Storage Platform Specifications

General IconGeneral
Drive TypesSSD, SAS
RAID SupportRAID 1, RAID 5, RAID 6, RAID 10
ConnectivityFibre Channel, iSCSI, FCoE
Form FactorRack-mounted
CategoryEnterprise Storage System
Data ReductionDeduplication and Compression (capabilities vary by model and software version)
Operating System CompatibilityWindows, Linux, UNIX, VMware
High AvailabilityRedundant components
ScalabilityScale-up and scale-out
ModelVirtual Storage Platform (VSP)

Related product manuals