8.3.4 DHW pipes connection
The connection between the DHW installation and the DHW connections of the indoor unit must
be done taking into account the following considerations:
1 Install a pressure and temperature relief valve at the DHW inlet connec tion (as close as possi-
ble to the tank) to provide the following functions.
Pressure protection
Non-return function
Shut-down valve
Filling
Draining
If not, an specic device for each function should be installed.
2 Install also a shut-down valve (eld supplied) in the DHW outlet connection, in order to make
easier any maintenance work.
NOTE
For more details, refer to the section “5.5 Space heating and DHW for YUTAKI M / YUTAKI Hydrosplit”.
8.3.4.1 Drain pipes connection
For a correct drainage, connect the drain pipe for the safety valve (located at the top rear side of
the unit) to the general draining system.
Safety valve
P&T relief valve
(Only for UK market)
NOTE
The safety valve is activated when water pressure reaches 3 bars.
Drain taps must be provided at all low points of the installation to permit complete drainage of
the circuit during servicing.
P&T relief valve is activated when water pressure reaches 7 bar and/or water temperature
reaches 96ºC