PMML0600 rev.0 - 06/2022
6
SETTING OF DIP SWITCHES AND RSW SWITCHES
ELECTRICAL AND CONTROL SETTINGS
6.2.1.8 DSW301
Test run mode (Only for RASM-(2/3)VRE)
RASM-(2/3)VRE: PCB2
DSW301 RASM-(2/3)VRE
Factory setting
4
321
Test run for pump down
4
321
Not available
4
321
Not available
4
321
Not available
4
321
Forced stoppage of compressor
4
321
NOTE
This operation is reset once the compressor is in Thermo-ON mode.
During the test run operation the units will operate continuously during 2 hours without Thermo-
OFF and the 3-minute guard for compressor protection will be eective.
Test run will start within 20 seconds aer setting DSW1 pin 1 to ON position.
6.2.1.9 DSW302
Optional Function setting (Only for RASM-(2/3)VRE)
RASM-(2/3)VRE: PCB2
DSW302 RASM-(2-3)VRE
Factory setting