SPACE HEATING AND DHW FOR YUTAKI M / YUTAKI HYDROSPLIT
DRAIN AND WATER PIPING
circuit to prevent the formation of air pockets. 
•  Check carefully for leaks in the water circuit, connections and circuit elements. 
5.5.9  Water quality
 ◆ General recommendations for Primary (Space Heating/Cooling) and Sec-
ondary (DHW) circuit.
 ! CAUTION
•  Water quality must be according to EU council directive 98/83 EC.
•  Water should be subjected to ltration or to a soening treatment with chemicals before 
application as treated water.
•  It is also necessary to analyse the quality of water by checking pH, electrical conductivity, 
ammonia ion content, sulphur content, and others. If the results of the analysis are not good, the 
use of industrial water would be recommended.
•  No antifreeze agent shall be added to the water circuit.
•  To avoid deposits of scale on the heat exchangers surface it is mandatory to ensure a high water 
quality with low levels of CaCO
3
.
Before water lling, sludge removal (for existing water networks), cleansing and rinsing (for 
an existing or new installations water networks) it is important to cleanse all hydraulic pipes 
to remove sludge and scale by using a specic designed product for cleaning central heating 
systems.
Also, its recommended to use a product inhibitor for protecting central heating systems against 
limescale and corrosion, always following manufacturer’s instructions and ensuring that the 
product is suitable for the material used in the water network and the YUTAKI unit.
When using chemical treatments and inhibitors always follow manufacturer’s instructions and 
ensure that the product is appropriate for the total water system. Using lling water that does 
not meet the stated quality requirements can cause a considerably reduce in service life. The 
responsibility will be out of Hitachi warranties.
The following water quality minimum requirement:
pH 6.5 to 8.5 -
Conductivity 10~500 µs/cm
Alkalinity 60~300 mg/l
Total Hardness
6 ~ 15 ºf H
0.6~1.5 mmol/l
60~150 mg CaCO
 /I
Chlorine <50  mg CI
¯
/I
Sulphate <50 (mg SO
2-
/l)