SETTING OF DIP SWITCHES AND RSW SWITCHES
ELECTRICAL AND CONTROL SETTINGS
6.2.2.10 DSW18
Not used
DSW18
RASM-(V)R(W)(1)E
HWM-WE
HWD-WE-220S(-K)
Factory setting
(Do not change)
6.2.2.11 SSW1
Remote/Local
SSW1 RASM-(V)R(1)E RASM-(V)RW1E
HWM-WE
HWD-WE-220S(-K)
Factory setting
Remote
Local
Remote
Local
Remote
Local
Local operation
Remote
Local
Not available Not available
NOTE
For YUTAKI M units RASM-(V)R(1)E using a Mirror box accessory, SWW1 must be changed to Local.
For YUTAKI M units RASM-(V)R(1)E: When DSW4#1 is OFF and it is not required any combination
with Mirror box accessory, set SSW1 to Local in order to operate without Remote Controller.
6.2.2.12 SSW2
Heat/Cool
SSW2
RASM-(V)R(W)(1)E
HWM-WE
HWD-WE-220S(-K)
Factory setting (Heat operation in case of Local)
Heat
Cool
Cool operation in case of Local
Heat
Cool
NOTE
Only for YUTAKI M units RASM-(V)R(1)E (Factory setting DSW4#1 is OFF).