11. Installation conguration
TCGB0075 rev.0 - 11/2012
136
11.1  System congurations
The YUTAKI S80 will generate hot water up to 80ºC and it is ideal for existing properties, in particular older establishments 
where higher water supply temperatures may be required to keep the house warm – as well as for new builds. It is designed 
for boiler substitution, offering heating and sanitary hot water all year round, without boiler back-up.
The YUTAKI S80 is designed to work in a mono-valent, mono-energetic or bi-valent heating systems. It provides efcient 
control and reduces energy use while maintaining comfort in the building.
The functionality of the YUTAKI S80 unit depends on the installed components and the selected conguration and it can 
be congured and upgraded to meet many application requirements.
  
Mono-valent system
The YUTAKI S80 is sized to provided 100% of the heating requirements on the coldest days of the year.
Example of Mono-valent system
  N O T E
• T
A 
: Outdoor ambient temperature.
• P
H 
: Heating capacity.
Air to water heat 
pump Capacity
Heat Demand
Air to water heat pump
Design point
P
H
T
A
  
Mono-energy system
The YUTAKI S80 is sized to provide approximately 80% of the heating requirements in the coldest days of the year. An 
auxiliary electric heater (as accessory) is used to provide the additional heating required on cold days.
Example of Mono-energy system
  N O T E
• T
A 
: Outdoor ambient temperature.
• P
H 
: Heating capacity.
• SP1/2/3:Heatersteps.
• Bivalent  point  can  be  set  through  the  LCD 
user’s interface.
Air to water heat 
pump + EH capacity
Air to water heat 
pump capacity
Heat demand
Air to water heat pump
Air to water 
heat pump + 
Heater
Bi-valent point
P
H
T
A