3.6 Electrical data
3.6.1 Considerations
Key words:
•  PH: Phase.
•  IPT: Total input power.
•  STC: Starting current: Less than maximum current.
•  RNC: Running current.
•  MC: Maximum current.
•  CB: Recommended circuit breaker.
•  ELB: Earth leakage breaker.
N O T E
• Heatinginlet/outletwatertemperaturecondition:55/65ºC.
• Outdoorambienttemperature(DB/WB):7/6ºC
• SpecicationsinthesetablesaresubjecttochangewithoutnoticeinorderthatHITACHImaybringthelatest
innovations to their customers.
3.6.2 Outdoor unit
Model Power supply
Applicable vol-
tage
Compressor and fan
motors
Max.
IPT
(kW)
MC
(A)
CB
(A)
ELB
(nº poles/A/mA)
U max.
(V)
U min
(V)
STC
(A)
IPT
(KW)
RNC
(A)
RAS-4HVRNME-AF
1~ 230V 50Hz 253 207
-
2.06 9.2 3.94 18.0 20
2/40/30RAS-5HVRNME-AF 2.62 11.6 5.75 23.0 25
RAS-6HVRNME-AF 3.27 14.5 5.86 23.0 25
RAS-4HRNME-AF
3N~ 400V 50Hz 440 360
2.06 3.0 4.72 7.0 15
4/40/30RAS-5HRNME-AF 2.62 3.9 6.76 11.0 20
RAS-6HRNME-AF 3.27 4.8 8.16 13.0 20
3.6.3 Indoor unit
Model Power supply
Applicable vol-
tage
Indoor unit system
Max.
IPT
(kW)
MC
(A)
CB
(A)
ELB
(nº poles/A/mA)
U max.
(V)
U min.
(V)
RNC
(A)
IPT
(kW)
RWH-4.0FSVNFE
1~ 230V 50Hz 253 207
12.2 2.73 5.41 24.0 32
2/40/30RWH-5.0FSVNFE 12.5 2.78 6.31 28.0 32
RWH-6.0FSVNFE 14.5 3.23 6.98 31.0 32
RWH-4.0FSNFE
3N~ 400V 50Hz 440 360
6.0 2.73 4.80 15.0 15
4/40/30RWH-5.0FSNFE 6.1 2.78 4.80 15.0 15
RWH-6.0FSNFE 7.0 3.23 4.80 15.0 15