3. General data
TCGB0075 rev.0 - 11/2012
58
3.2.2 RAS-(4-6)HRNME-AF
Model RAS-4HRNME-AF RAS-5HRNME-AF RAS-6HRNME-AF
Electrical power supply 3N~ 400V 50Hz
Color (Munsell code) - Natural gray (1.0Y8.5/0.5)
Sound pressure level dB(A) 46 48 50
Sound power level dB(A) 65 67 69
Outside measu-
rements
Height mm 1,380 1,380 1,380
Width mm 950 950 950
Depth mm 370 370 370
Net weight kg 107 108 108
Refrigerant - R-410A
Flow control - Microprocessor-controlled expansion valve
Compressor - DC inverter driven
Quantity - 1 1 1
Power kW 2.20 3.00 3.00
Heat exchanger - Multi-pass cross-nned tube
Condenser fan - Propeller fan
Quantity - 1+1 1+1 1+1
Air ow rate m³/min 80 90 100
Power W 70+70 70+70 70+70
Refrigerant pipe connection - Flare-nut connection (factory supplied)
Size
Liquid piping
mm
(in)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Ø9.53
(3/8”)
Gas piping
mm
(in)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Ø15.88
(5/8”)
Refrigerant charge kg 3.90 4.00 4.00
Maximum current A 7.0 11.0 13.0
Packaging measurements m³ 0.70 0.70 0.70
N O T E
The sound pressure level is based on following conditions:
• 1meterfromthefrontalsurfaceoftheunit;1.5metersfromoorlevel.
• Voltage of the power source is 400V.
Theabovedataismeasuredinananechoicchamber,soreectedsoundshouldbetakenintoconsideration