3. General data
TCGB0075 rev.0 - 11/2012
60
3.3.2 RWH-(4.0-6.0)FSNFE
Model RWH-4.0FSNFE RWH-5.0FSNFE RWH-6.0FSNFE
Electrical power supply - 3N~ 400V 50Hz
Pump input power W 140 140 140
Maximum current A 15.0 15.0 15.0
Nominal water ow (condition 
)
m³/h 1.7 2.1 2.4
Unit
dimensions
Height mm 706 (*1)
Width mm 595
Depth mm 695
Packaging
dimensions
Height mm 837
Width mm 770
Depth mm 720
Net weight kg 162 167 167
Packaging dimensions 0.46
Refrigerant - R-134a
Flow control - Microprocessor-controlled expansion valve
Compressor type - DC inverter driven hermetic scroll
Quantity - 1 1 1
Power kW 3.0 3.0 3.0
Refrigerant charge kg 2.5
Refrigerant pipe connection - Flare nut connection (*2)
Dimensions
Liquid pipe mm Ø 9.53 (3/8”)
Gas pipe mm Ø 15.88 (5/8”)
Water pipe connection - Screwed connections
Space hea-
ting
Inlet diameter inch Flexible pipe (G 1” male)
Outlet diameter inch Flexible pipe (G 1” male)
DHW
Inlet diameter inch Flexible pipe (G 3/4” male)
Outlet diameter inch Flexible pipe (G 3/4” male)
Expansion vessel volume l 12
Color - White (RAL 9016)
N O T E
• (*1): Dimensions with the minimum mounting foot height. This value can be adjusted up to +30 mm.
• (*2):Refrigerantliquid/gaspipingaccessoryisfactory-suppliedinordertoassistintherefrigerantpipecon-
nection.Inthiscasetheconnectiontotheeldrefrigerantpipemustbebrazed.Formoreinformation,please
refer to the Installation and operation manual.