10. Electrical wiring
TCGB0075 rev.0 - 11/2012
121
10
10.4 Setting of DIP switches and RSW switches
10.4.1 Outdoor unit
Location of DIP switches and RSW switches
The PCB in the outdoor unit is operated with different dip switches, rotary switches and push switches.
Position switches at the PCB:
RAS-(4-6)H(V)RNME-AF
SEG1
DSW6
DSW1
LED2
SW1
PSW2
PSW1
PSW3
DSW4
DSW3
RSW
LED1
DSW2
LED3
DSW5
JP1
JP6
Function of the of DIP switches and RSW switches
N O T E
• Themark“■”indicatesthepositionofdipsswitches.
• Nomark“■”indicatespinpositionisnotaffecting.
• Theguresshowthesettingsbeforeshipmentorafterselection.
C A U T I O N
Beforesettingdipsswitches,rstturnthepowersourceoffandthensetthepositionofthedipsswitches.In
case of setting the switches without turning the power source off, the contents of the setting are invalid.
DSW1: Test run
Function Setting position
Setting before shipment
Test run for pumping down
Test run for heating
Forced stop of compressor
The compressor is OFF during this operation.
N O T E
• This operation is reset once the compressor is in Thermo-ON mode.
• During the test run operation the units will operate continuously during 2 hours without Thermo-OFF and the
3-minute guard for compressor protection will be effective.