2. Features and benets
TCGB0075 rev.0 - 11/2012
49
2
2.6.3  Swimming pool combination control 
When  the  swimming  pool  operation  is  required,  the  swimming  pool  pump  starts  to  operate  giving  the  swimming  pool 
pump feedback. In this situation, the 3-way valve of the DHWT is not activated and the 3-way valve for the swimming pool 
changes its normal position diverting to the swimming pool heat exchanger, allowing to heat the swimming pool water to 
a confortable value.
The swimming  pool operation has the  lowest priority of the  system and only  will be possible when  space heating and 
DHWT are not required.
2.6.4  Flexible water pumps control
  
Two different water pump modes
The pump control can be set to standard or economic mode.
•  Standard mode: Pump will always be in operation when space heating is enabled, but when space heating is disa-
bled using LCD user’s interface or Thermostat OFF (intelligent thermostat only), pump must be switched OFF and 
only will be switched ON by DHW heating request.
•  Economic mode: When the system has reached the required temperature, or the system is stopped, the water pump 
will be stopped (using the thermostat; no other operation is required).
  
Pump and motorized valve seizure protection (Optional function)
This function helps to prevent these components from sticking during long periods of inactivity by running every week the 
components during a short period.
2.6.5  Other optional functions
  
2nd. outdoor temperature sensor (Accessory) (Improved for YUTAKI S80)
In the cases where the outdoor unit is installed into a location where its own outdoor ambient temperature sensor can not 
give a suitable temperature measurement to the system, it is available the 2nd outdoor ambient temperature sensor as 
accessory.
So, the 2nd outdoor ambient temperature sensor shall be located in a proper place for getting most representative outdoor 
ambient temperature.
NEW
-By means of DSW setting, it can be selected the preferable sensor for each circuit. The possibilities are:
•  Auxiliary sensor instead of outdoor unit sensor for both circuits.
•  Outdoor unit sensor for circuit 1; Auxiliary sensor for circuit 2.
•  Auxiliary sensor for circuit 1; Outdoor unit sensor for circuit 2.
  N O T E
For more information, please refer to DSW setting section on Service Manual.
  
Tariff switch input
This function allows an external tariff switch device to switch OFF the heat pump during peak electricity demand period. 
Depending on the setting, the heat pump or DHWT will be blocked when signal is open/closed.
Additionally, it’s possible to set that the boiler will be enabled instead heat pump when this mode is ON.