7847i-E Installation and Setup Guide
3-10
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
23
Keypad Address
(28)_
[01-30]
Must be programmed if using Direct Wire
downloading. Enter the appropriate device
address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel. If a full
enhanced graphic interface to the system is
desired, the keypad must also be enabled as an
AUI (Advanced User Interface) device. DO NOT
connect to an actual keypad (or any other
device) assigned to this address.
2. This address must be unique from the "Device
Address" entered in Prompt 21.
24
Supervision
(24 Hours)_
24 Hours
1 Hour
6 Min
3 Min
90 Sec
CN 90 Sec
75 Sec
None
30 Day
The receiver must hear at least one supervisory
message from the module during this supervision
period; otherwise, the receiver notifies the central
station that a communication failure has occurred.
If the supervision period is changed after
registration, you must re-register the module.
Press the [space] key to scroll through choices.
Must be set to:
3 minutes for UL Comm Fire/Burg or ULC
Active Channel Security.
24hrs for ULC Passive channel security
25
Old Alarm Time
10 Minutes_
10 Min.
15 Min.
30 Min.
1 Hr
2 Hrs
4 Hrs
8 Hrs
12 Hrs
24 Hrs
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is
not validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL NOTE: Must be 10 minutes.
26
IP Flt Time
(60 mins)_
[00-99]
Enter the time delay (01-99) in minutes before the
7847i-E notifies the control panel that there is loss
of contact with the network, or enter 00 if you do
not want the unit to alert the control panel of loss
of contact with the network. The unit will alert the
control panel of the loss of contact via a dedicated
status message.
UL/ULC NOTE: Must be one (01) minute.