Section 3: Programming the 7847i-E
3-11
27
Flt Rel ON Y/N
(N)_
[Y], [N]
During normal system operation the open
collector fault output will change states (open or
ground) on a fault condition. The change of state
depends on whether (Y) or (N) is used during
programming.
• Tamper *
• Loss of Network Connectivity *
• Message Communication Failure
• Device Not Registered
*Fault must be enabled in programming
for these conditions (tamper & loss of
network) to trigger the fault output
Choosing Flt Rel ON (Y),
• Provides a ground during normal
operation.
• Provides an open during a fault.
• “Failsafe mode” (if the radio loses power,
the fault output opens, de-energizing the
relay)
Choosing Flt Rel ON (N),
• Provides an open during normal
operation.
• Provides a ground during a fault
condition.
This mode is lower power consumption.
UL/ULC NOTE: Must be set to "Y."
28
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report on zone 8 when the
module detects a tamper condition. A tamper
restore is automatically sent when the tamper
condition clears.
UL/ULC NOTE: Must be “Y” for commercial
29
Lynx Panic Y/N
(N)_
[Y], [N]
Applies only if used with control communication
device (LRR) trigger connected to the module's
zone terminal.
Reports a Panic alarm on zone 3 when the
module detects a single pulse on zone 1.
No restores are generated for a Panic alarm.