Section 3: Programming the 7847i-E
3-15
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
56
Rpt Zn5 ONLY if
Armed (N)_
2-
4204
only
[Y], [N]
Reports alarms on zone 5 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-
4204 mode) is triggered (armed).
If [N], always reports alarms on zone 5.
57
Enable Zn6 Y/N
(N)_
4204
only
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 63: "Enable Zn7."
58
Zn6 Trigger Type
(V+)_
4204
only
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL: V+ must be set as inverted and V- as non-
inverted
59
Invert Zn6 Y/N
(N)_
4204
only
[Y], [N]
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
60
Restore Zn6 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 6.
61
Delay Zn6 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 6.
UL: Must be 00
62
Rpt Zn6 ONLY if
Armed (N)_
[Y], [N]
Reports alarms on zone 6 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 6.
63
Enable Zn7 Y/N
(N)_
4204
only
[Y], [N]
Enables alarm reporting for zone 7.
If [N], skip to Prompt 70: "Use DHCP."
64
Zn7 Trigger Type
(V+)_
4204
only
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL: V+ must be set as inverted and V- as non-
inverted
65
Invert Zn7 Y/N
(N)_
4204
only
[Y], [N]
Inverts the alarm and normal states of the zone 7
trigger; otherwise uses normal input signal.
66
Restore Zn7 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 7.
Zone Trigger mode: This question will only be
displayed if zone 7 is not used as the conditional
(arming) trigger zone.
67
Delay Zn7 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 7.
Zone Trigger mode: This question will only be
displayed if zone 7 is not used as the conditional
(arming) trigger zone.
UL: Must be 00
68
Rpt Zn7 ONLY if
Armed (N)_
[Y], [N]
Reports alarms on zone 7 ONLY if the conditional
zone (zone 4 in 4204 mode; zone 8 in 2-4204 mode)
is triggered (armed).
If [N], always reports alarms on zone 7.
2-4204 mode: If any zone is programmed to "Report
Only if Armed," or if tamper is enabled, skip to
Prompt 70: "Use DHCP."
69
Delay Zn8 (secs)
(00)_
2-
4204
only
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 8.
UL: Must be 00