7847i-E Installation and Setup Guide
3-14
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
39
Restore Zn2 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 2.
40
Delay Zn2 (secs)
(00)_
[01-15]
[00]=no delay
Defines the reporting delay in seconds for zone 2.
UL: Must be 00
41
Rpt Zn2 ONLY if
Armed (N)_
[Y], [N]
Reports alarms on zone 2 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 2.
If Lynx Panic is enabled, then skip to Prompt 46: "Rpt Zn3 ONLY if Armed."
42
Zn3 Trigger Type
(V+)_
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL: V+ must be set as inverted and V- as non-
inverted
43
Invert Zn3 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 3
trigger; otherwise uses normal input signal.
44
Restore Zn3 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 3.
45
Delay Zn3 (secs)
(00)
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 3.
UL: Must be 00
46
Rpt Zn3 ONLY if
Armed (N)_
[Y], [N]
Reports alarms on zone 3 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to "Report
Only if Armed," skip to Prompt 57: "Enable Zn6."
47
Zn4 Trigger Type
(V+)_
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL: V+ must be set as inverted and V- as non-
inverted
48
Invert Zn4 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 4
trigger; otherwise uses normal input signal.
49
Restore Zn4 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 4.
50
Delay Zn4 (secs)
(00)
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 4.
UL: Must be 00
51
Rpt Zn4 ONLY if
Armed (N)_
2-
4204
only
[Y], [N]
Reports alarms on zone 4 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 2-
4204 mode) is triggered (armed).
If [N], always reports alarms on zone 4.
52
Zn5 Trigger Type
(V+)_
(EOLR)
(V+)
(V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL: V+ must be set as inverted and V- as non-
inverted
53
Invert Zn5 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.
54
Restore Zn5 Y/N
(Y)_
2-
4204
only
[Y], [N]
Enables restore reporting for zone 5.
55
Delay Zn5 (secs)
(00)_
2-
4204
only
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 5.
UL: Must be 00