Accenta/Optima Engineers Manual
18
Menu Options
The full menu structure for the panel can only be accessed while in Engineer program mode. The structure is
shown in the following table:
Table 2. Menu Options
Menu Options
Enter Engineer program mode. Press [9] [9] [9] [9].
0 = Walk Test
The walk test function allows each detector to be checked in order to verify that they are functioning correctly.
A tone is generated as each zone is activated (opened).
LED keypad
Press [0] for menu Walk Test.
Press . Zones 1-8 are off
When a zone is sucsessfully tested, the LED is on.
Zones are added to list as eachone is activated.
The Tamper LED comes on when tested.
Press to leave the menu or to restart
the Walk Test.
LCD keypad
Press for menu Walk Test.
Press or [0]. Zones 1-8 have a zero (0)below
each number.
When a zone is sucsessfully tested, number 1replaces the 0.
Zones are added to list as eachone is activated.
Press to leave the menu or to restart the Walk Test.
MENU OPTIONS
0 = Walk Test 6 = Zone Names
1 = Alarm Test 7 = Timers
2 = Test Outputs 8 = Codes
3 = System Flags C = View Event Log
4 = Time and Date O = Omit Allow & Double
Knock
5 = Language P = Programmes
or [0]
0>Walk Test
12345678 TP
00000000 00
0>Walk Test
12
3
4
5
6
7
8
12
3
4
5
6
7
8