48 Installation instructions / ACS-2 plus
Example:
Example:
1. 9-bit AC/CU Prot.
2.=>DIN prot.
3. RDT prot.
4. Event prot.
Status: Addr: 32; GAddr: 30; 19200 Baud
Change? Y/N:_
The current value is marked with "=>". To modify the values enter "y" and confirm
with Enter. Then you can select one of the consecutive numbers.
Settings and their use:
9-bit AC/CU prot.: ------
DIN prot.: Direct connection to RS232 (e.g., PC/notebook) or interface
converter
RDT prot.: For modem operation
Event prot.: For network operation via Ethernet interface
The following information can be checked and modified if necessary depending on
the selected protocol:
Baud rate: The current value is marked with "=>".
The value can be changed by entering “y” + Enter (at the question
Change? Y/N) and the consecutive number of the desired baud rate
(the factory setting is 19200).
Address: The current address and the permitted address range are displayed.
The value can be changed by entering “y” + Enter (at the question
Change? Y/N) and the desired address (the factory setting is 32).
Group address: The current group address and the permitted address range are
displayed. The value can be changed by entering “y” + Enter (at the
question Change? Y/N) and the desired address (the factory setting
is 30).
Difference between address - group address:
A maximum of 32 controllers can be managed via the address (addresses
1 - 32). An additional group address is used to extend the address range and
the number of controllers managed (max. 30 x 32 = 960 (MultiAccess for
Windows can currently manage a maximum of 512 controllers)).
Group address Addresses
11 - 32
21 - 32
31 - 32
41 - 32
etc.
30 1 - 32
With the event protocol, the following fields must be checked or modified, if