EasyManuals Logo

Honeywell BACnet User Manual

Honeywell BACnet
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
BACNET® FIXED FUNCTION THERMOSTAT
31-00099—01 14
APPLICATION 10 – HEAT PUMP (AIR TO AIR)
Features and Notes
Three modes of schedule control set by AV-123 –
0 = Single point with offset during occupancy,
1 = Dual setpoint residential – wake, leave, return & sleep,
2 = Dual setpoint with offset occupancy.
BACnet MS/TP compliant.
English or metric units.
Outputs are disabled if BV-2 is off.
Disable operator access via the display to the schedule
by setting BV-102 to off.
Onboard schedule can be enabled or disabled (BV-40).
Heating and cooling are disabled if the fan is off.
Use up and down arrows on the display to force the unit
into occupancy for four hours.
Setpoint mode emulates residential thermostat operation.
Fan can be set to run continuously or cycle on and off for
heating or cooling demands while in Occupancy mode
(AV-17).
Fan speed will ramp between 0-100% depending on
cooling and heating demands
Fan speed selected upon the following settings -
Low Speed – at 20% demand (adjustable in AV-46)
Medium Speed – at 40% demand (adjustable in AV-85)
High Speed – at 70% demand (adjustable in AV-89)
Fan speed deadband set at 2%
Analog economizer control is defaulted to disabled.
Economizer requires a supply air sensor connected to AI-2.
The cooling and heating valves can be controlled by
either a cooling and heating signal or via the supply air
temperature (BV-15).
Electric heater is enabled if heating demand exceeds 75%.
Humidity control can be enabled for un-occupancy
(BV-12 & BV-53).
Use a 10K Type II Thermistor Sensor for AI-2 Input.
If the BACnet FF detects that the door or window contact
is open during occupancy for a period longer than what
is defined in the standby delay (AV-20) it will put the unit
into standby mode.
To configure AI-0 as a sensor set the following
parameters.
SINGLE STAGE ELECTRIC HEAT AND 3 SPEED FAN
Inputs
AI-0::
Space Sensor or Outside Air
Sensor (optional)
AI-2:: Supply Air Sensor
(optional,
required for Economizer control)
BI-1:: PIR/Door/Window Sensor
(optional)
BI-2:: Condensate Sensor (optional)
Outputs
BO-0:: Fan Low Speed
BO-1:: Fan Medium Speed
BO-2:: Fan High Speed
BO-3:: Heat Pump Compressor
BO-4:: Reversing Valve
BO-5:: Auxiliary Heat
AO-0:: Economizer (optional analog)
0-10V or 4-20mA
AO-1:: Fan Speed Control (optional)
4-20mA VFD/SCR
Note: Any I/O listed as “optional” will
require a BV to be set. Refer to the
sequence of operations outlined in
the BACnet FF Thermostat System
Engineering Guide, 31-00098.
MS/TP Network
Compr.
Rev.
Valve
Digital
Digital
Digital
Supply
Fan
Electric
Heater
Digital
Digital
Space or Outside
Temperature Sensor
(optional)
Supply
Temperature Sensor
(required for economizer
control)
PIR/Door/Window Sensor
(optional)
Condensate Sensor
(optional)
BV-47 (PS) BV-32 (Sr)
Space Temperature Off On
Outside Temperature On Off
Fan F 1 SS
Fan F 2 SS
Fan F 3 SS
HP Compr
Rev Vlv
Econ
Controller Terminations
HPH1 AP 10
GND
5
BO 0
BO 1
BO 2
BO 3
BO 4
BO 5
G1
G2
G3
Y1
O/B
EC
0-10Vdc
4-20ma
AO 0
C
RC24VAC
1
24V
Com
Htg Stg 1
W1
AO 1
Com
14
BI/AI 1
COM
BI/AI 2
COM
BI/AI 0
Sensor
SA Sensor
Optional
Standby
N.C. or N.O.
Optional
Condensate
alarm or fail
VC
VFD /SCR
4-20ma
* Optional space or outside temperature sensor.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell BACnet and is the answer not in the manual?

Honeywell BACnet Specifications

General IconGeneral
Communication ProtocolBACnet MS/TP
Power Supply24 VAC/VDC
DisplayLCD (backlit)
MountingWall Mount
Operating Temperature32°F to 122°F (0°C to 50°C)

Related product manuals