BACNET® FIXED FUNCTION THERMOSTAT
31-00099—01 8
APPLICATION 4 – AIR CONDITIONING UNIT
Features and Notes
Three modes of schedule control set by AV-123 –
0 = Single point with offset during occupancy,
1 = Dual setpoint residential – wake, leave, return & sleep,
2 = Dual setpoint with offset occupancy.
BACnet MS/TP compliant.
English or metric units.
Outputs are disabled if BV-2 is off.
Disable operator access via the display to the schedule
by setting BV-102 to off.
Onboard schedule can be enabled or disabled (BV-40).
Heating and cooling are disabled if the fan is off.
Use up and down arrows on the display to force the unit
into occupancy for four hours.
Setpoint mode emulates residential thermostat
operation.
Standby mode enables power saving if no motion is
detected while in occupancy.
If condensation is detected, the compressor is held off
with the optional condensate input.
By default the economizer control is set for analog. To
use three point floating control set a value in AV-63
(Economizer Stroke Time).
The economizer control requires a supply air sensor
connected to AI-2:.
One stage of auxiliary heating.
Use 10K Type II Thermistor sensors for analog inputs.
Electric heat is enabled when heating demand is > 65%.
To configure AI-0 as a sensor set the following
parameters.
COMPRESSOR, SINGLE STAGE ELECTRIC HEAT
Inputs
AI-0:: Space Sensor or Outside Air
Sensor (optional)
AI-2::
Supply Air Sensor (optional,
required for economizer control)
BI-1:: PIR/Door/Window Sensor
(optional)
BI-2:: Condensate Sensor (optional)
Outputs
BO-0:: Fan
BO-1:: Compressor
BO-2:: Not used
BO-3:: Electric Heat (optional)
BO-4:: Economizer Open (optional for
floating control)
BO-5:: Economizer Close (optional for
floating control)
AO-0:: Economizer (optional analog)
0- 10V or 4-20mA
AO-1:: Fan Speed Control (optional)
4-20mA
Note: Any I/O listed as “optional” will
require a BV to be set. Refer to the
sequence of operations outlined in
the BACnet FF Thermostat System
Engineering Guide, 31-00098.
MS/TP Network
Compr.
Digital
Digital
Supply
Fan
Electric
Heater
Digital
Digital
Space or Outside
Temperature Sensor
(optional)
Supply
Temperature Sensor
(required for economizer
control)
PIR/Door/Window Sensor
(optional)
Condensate Sensor
(optional)
BV-47 (PS) BV-32 (Sr)
Space Temperature Off On
Outside Temperature On Off
Fan
Cmp Stg 1
Htg Stg 1
Econ Opn
Econ
Econ Cls
Controller Terminations
A1H1 AP 4
GND
5
BO 0
BO 1
BO 2
BO 3
BO 4
BO 5
G
Y1
W1
EC
EC
EC
0-10Vdc
AO 0
C
RC24VAC
1
24V
Com
AO 1
Com
14
BI/AI 1
COM
BI/AI 2
COM
BI/AI 0
Sensor *
SA Sensor
Optional
Standby
N.C. or N.O.
Optional
Condensate
alarm or fail
VC
VFD /SCR
4-20ma
* Optional space or outside temperature sensor.
4-20ma

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell BACnet and is the answer not in the manual?

Honeywell BACnet Specifications

General IconGeneral
Communication ProtocolBACnet MS/TP
Power Supply24 VAC/VDC
DisplayLCD (backlit)
MountingWall Mount
Operating Temperature32°F to 122°F (0°C to 50°C)