EasyManuals Logo

Honeywell BACnet User Manual

Honeywell BACnet
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
BACNET® FIXED FUNCTION THERMOSTAT
23 31-00099—01
FIELD SERVICE MODE SETTINGS
Items listed below are in order of display via the "Field Service Mode" on the BACnet FF Screen.
Service
Code
Object
Instance
Default
Value
Range Purpose/Function Applications
parameter
applies to.
UC AV-95 85 45.0 to 99.0 Unnoccupied Cooling Setpoint All
UH AV-96 55 45.0 to 84.5 Unnoccupied Heating Setpoint All
CO AV-93 2 0.0 to 20.0 Cooling Offset All
HO AV-94 1 0.0 to 20.0 Heating Offset All
CS AV-99 Calculated From AV-90 Occupied Cooling Setpoint All
HS AV-100 Calculated From AV-90 Occupied Heating Setpoint All
AL AV-97 4 0 to 9.5 Override Limit (hours) All
HI AV-91 78 0.0 to 127.0 Setpoint High Limit All
LO AV-92 62 0.0 to 89.5 Setpoint Low Limit All
SP AV-90 70 Restricted to range set by
AV-92 & AV-91.
Occupant Selected Space Temperature Setpoint. All
AP AV-49 Set this to select the required Application Application Selection range 0 to 18 All
OE BV-2 Off Set to On after completing all
other settings.
Enable Outputs All
HC BV-21 Off On = Heating. Off = Cooling. Reversing Valve Action Heating-Cooling. 0-3, 10
FC AV-17 1 1 = Fan runs continuous,
2 = Fan Cycles with Heating,
3 = Fan Cycles with Cooling.
All
CC AV-26 12 1 to 1440 AC-HP Compressor Cycle Time (mins) 0-3,10
C0 AV-27 3 AC-HP Compressor Minimum On Runtime (mins) 0-3,10
CF AV-18 3 AC-HP Compressor Minimum Off Runtime (mins) 0-3,10
Hc AV-28 3 1 to 1440 Heating Stages Cycle Time (mins)
(if set to 0 or less this will disable heating)
0-5,9,10,13,16,18
h0 AV-29 1 Heating Stages Minimum runtime (mins) 0-5,9,10,13,16,18
hF AV-80 60 Heating Stages Minimum Off runtime (seconds) 0-5,9,10,13,16,18
2C AV-37 3 1 to 1440 2 Position Valve Cycle Times (mins) 8,9,14-16,18
2c AV-38 1 2 Position Valves Minimum runtime (mins) 8,9,14-16,18
c5 AV-64 0 0 to 180 Cooling Valve Stroke Time. (seconds) 6-9,11-18
h5 AV-65 0 0 to 180 Heating Valve Stroke Time. (seconds) 6-9,11-18
2P AV-34 1 1=On/Off. 2=Analog to Binary 2 Position Valve Mode 8,9,14-16,18
FA BV-55 Off On/Off Enable Fan Control display All
cL AV-70 55 Cooling Lockout Temp All
hL AV-72 62 Heating Lockout Temp All
P5 BV-47 Off On/Off Off = Enable AI-0 input as a Space Temperature Sensor,
On = use the internal BACnet FF sensor (AV-104).
0-6,10,17
Sr BV-32 Off On/Off On = Enable AI-0 input as Space Temperature,
Off = OAT
0-6,11,17
F1 AV-46 20 Set by DDC AV-80 minus 2% Auto Fan Start Demand % All
F5 AV-5 0 Fan stop delay (seconds) All
F2 AV-85 0 Medium Speed Fan Setpoint All
F3 AV-89 0 High Speed Fan Setpoint All
uL BV-3 Off On/Off Reverse Standby Logic. All
50 AV-19 4 0 to 12 Standby Heating SetPoint All

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell BACnet and is the answer not in the manual?

Honeywell BACnet Specifications

General IconGeneral
Communication ProtocolBACnet MS/TP
Power Supply24 VAC/VDC
DisplayLCD (backlit)
MountingWall Mount
Operating Temperature32°F to 122°F (0°C to 50°C)

Related product manuals