EasyManuals Logo

Honeywell BACnet User Manual

Honeywell BACnet
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
BACNET® FIXED FUNCTION THERMOSTAT
31-00099—01 22
APPLICATION 18 – FAN COIL UNIT – 2 PIPE
Features and Notes
BACnet MS/TP compliant.
English or metric units.
Outputs are disabled if BV-2 is off.
Disable operator access via the display to the schedule
by setting BV-102 to off.
Onboard Schedule can be enabled or disabled (BV-40).
Heating and cooling are disabled if the fan is off.
Use up and down arrows on the display to force the unit
into occupancy for four hours.
Setpoint mode emulates residential thermostat
operation.
Fan can be set to run continuously or cycle on and off for
heating or cooling demands while in occupancy mode
(AV-17).
Fan control is either start/stop or variable speed control.
The cooling or heating valve can be controlled by either a
cooling or heating signal or via the supply air
temperature (BV-15).
Humidity control can be enabled for un-occupancy
(BV-53).
If door or window contacts are open longer than the
delay time (AV-20) the unit goes into standby mode.
Humidity control can be enabled for un-occupancy
(BV-12 & BV-53).
Use 10K Type II Thermistor sensors for the water and
supply air temperature sensors.
TWO POSITION, THREE POINT FLOATING, OR ANALOG COOLING OR HEATING VALVE, ELECTRIC HEATER, ON/OFF OR VFD FAN
Inputs
BI-1::
PIR/Door/Window Sensor
(optional)
AI-0:: Supply Air Temperature
AI-2:: Supply Water Temperature
Sensor
Outputs
BO-0:: Fan On/Off
BO-1:: Not Used
BO-2:: Cooling/Heating Valve
2 Position Open/Close
BO-3:: Cooling/Heating Valve Open
3 Point Floating
BO-4:: Cooling/Heating Valve Close
3 Point Floating
BO-5:: Auxiliary Electric Heating Coil
AO-0:: Analog Modulating Cooling or
Heating Valve 0-10V or
4-20mA (optional)
AO-1:: Fan Speed Control (optional)
4-20mA
Note: Any I/O listed as “optional” will
require a BV to be set. Refer to the
sequence of operations outlined in
the BACnet FF Thermostat System
Engineering Guide, 31-00098.
MS/TP Network
Digital
2 Position Open/Close, 3 Point Floating or Analog
Digital or VSD
Electric
Heater
Digital
Supply Air
Temperature Sensor
(optional)
Standby Detection
(optional)
Strap on Supply Water
Temperature Sensor (optional)
Fan
Clg/Htg Vlv
Clg/Htg V Op
ELEC COIL
Clg/HTG Vlv
Controller Terminations
2PFC AP 18
GND
5
BO 0
BO 1
BO 2
BO 3
BO 4
BO 5
AO 1
G1
Y1
Y2
Y3
W1
EC
0-10Vdc
Com
14
AO 0
C
RC24VAC
1
24V
Com
BI/AI 1
COM
BI/AI 2
COM
BI/AI 0
EC/VC
VC
FAN VFD
4-20ma
4-20ma
Com
Y4
W1
Clg/Htg V Cl
Strap on C /O Temp Sensor
Required to monitor water temp in supply pipe
SA Sensor
Optional
Standby
N.C. or N.O.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell BACnet and is the answer not in the manual?

Honeywell BACnet Specifications

General IconGeneral
Communication ProtocolBACnet MS/TP
Power Supply24 VAC/VDC
DisplayLCD (backlit)
MountingWall Mount
Operating Temperature32°F to 122°F (0°C to 50°C)

Related product manuals