EasyManuals Logo

Honeywell BACnet User Manual

Honeywell BACnet
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
BACNET® FIXED FUNCTION THERMOSTAT
31-00099—01 24
LIST OF MAIN DEVICE OBJECTS
Not accessed via the touchscreen. These are set up with default values.
Fan Control Zone Control
Device Object Label Device Object Label
AV-39 Fan Speed Demand (Analog) % AV-103 Outside Air Temp
AV-5 Fan Stop Delay (Sec) AV-104 Space Temp from (BMS)
AV-82 Fan Runtime AV-12 Supply Air Temp
AV-85 Medium Speed Fan Start SP AV-123 Schedule Module
AV-86 Filter Runtime AV-36 Space Temp used for PI Calc
AV-89 High Speed Fan Start SP BV-124 System Auto Selected
BV-16 Filter Alarm BV-133 Enable Internal Schedule
BV-5 Fan Status BV-32 Enable Remote Sensor (AI-2)
BV-59 Fan Auto - On BV-4 In Standby Mode
BV-72 Fan 3 speed - Low BV-40 Occupied Command
BV-73 Fan 3 speed - Medium BV-47 Enable Remote Sensor (AI-0)
BV-74 Fan 3 speed - High BV-56 Enable BMS Scheduling
BV-80 Enable Fan Speed Control Heating and Cooling Signals
Compressor Control AV-0 Heating Signal
AV-21 Compressor 1 Starts AV-1 Cooling Signal
AV-22 Compressor 2 Starts AV-105 Sensed Humidity
AV-40 AC HP Mode Control AV-13 Heating Valve Demand
AV-68 AC HP Compr Start Demand % AV-18 AC-HP Compr. Min Off (mins)
AV-69 AC HP Compr Stop Demand % AV-27 AC-HP Compr. Min On (mins)
AV-81 Runtime HP Comressor (App 10) AV-41 Heat Signal Proportional Gain
AV-87 Runtime Cooling Stage 1 AV-42 Heating Signal Integral Gain
AV-88 Runtime Cooling Stage 2 AV-43 Cool Signal Proportional Gain
BV-21 Reverse Valve Action, 1 = cool AV-44 Cooling Signal Integral Gain
BV-22 1 = Cooling Locked Out AV-57 Calc. Compr. Off time (sec)
BV-27 1 = Heating Locked Out AV-58 Calc. Compr. Cycle time (sec)
BV-6 HP Fun Request AV-59 Calc. Compr. Mins on (sec)
BV-7 Fan Request (AC Cooling) AV-8 Cooling Valve Demand
BV-31 WS HP Water Loop OK AV-83 Runtime Heat Stage 1
Economizer Control AV-84 Runtime Heat Stage 2
AV-10 Economizer Position BV-1 1 = In Heating Mode
AV-63 Econ. Damper Stroke Time BV-12 1 = Dehum Mode is On
AV-60 Supply Air Low temp Limit BV-52 RH Fan Circ Cycle time (mins)
AV-66 Econ. Min. Position BV-27 Heating Lockout
AV-11 Float Point Econ. Position BV-28 Cooling Lockout
BV-20 Supply Air Low Limit Alarm BV-24 Supply Temperature Valid
Occupancy/Standby Residential Mode
BV-4 In Standby Mode AV-129 Sets the number of occupancy periods,
2 = wake and sleep,
4 = wake, leave, return and sleep.
BV-63 Door Open
BV-62 No Motion Since Door Closed
NOTE: This is a selection of some of the device objects.
For the full list refer to the BACnet FF Thermostat
System Engineering Guide, 31-00098.
BV-149 Wireless Installed
BV-67 Occupied
BV-60 Window/Door Open (Wireless)
BV-61 No Motion Since Dr Clsd (Wireless)
AV-20 Standby Delay (Sec)
BV-81 Hotel Mode

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell BACnet and is the answer not in the manual?

Honeywell BACnet Specifications

General IconGeneral
Communication ProtocolBACnet MS/TP
Power Supply24 VAC/VDC
DisplayLCD (backlit)
MountingWall Mount
Operating Temperature32°F to 122°F (0°C to 50°C)

Related product manuals