บริษัท เอดีดี เฟอร์เนส จํากัด 
ADD FURNACE CO.,LTD. 
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170 
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258 
https://www.add-furnace.com E-mail: sales@add-furnace.com 
 
 
   
ADJUSTMENTS AND CHECKOUT 
 
Adjust Detector Sighting 
With the flame  detector  installed and the  burner  running, 
adjust the sighting position of the detector for optimum flame 
signal. It is suggested that a volt-Ohm meter with a minimum 
sensitivity of one megohm/volt and a zero to fi e or ten Vdc 
scale  be  used  for  R7861  amplifier  flame  signal 
measurements. 
Measure the flame signal as illustrated in Fig. 11. Be careful 
to make the proper connections of positive (red) meter lead 
to positive (+) control jack and negative (black) meter lead   
to negative (-) or (-Com) jack with 7800 SERIES controls. 
When the 7800 SERIES control has the keyboard display 
module,  a  zero  to  five  Vdc  voltage  is  displayed  on  the 
module. On SLATE devices expect zero to 8 Vdc. 
NOTE:   The flame Signal must be stable. 
Use a multimeter when measuring the flame 
signal or read the display. 
Move the detector and sight pipe around to sight the flame 
from various positions and angles. Try to get a maximum 
steady (or stable) reading on the meter. The signal must be 
above the minimum acceptable voltage listed in Table 1. 
Measure the flame signal for the pilot alone, the main burner 
flame alone, and both together (unless monitoring only the 
pilot flame when using an intermittent pilot, or only the main 
burner flame when using direct spark ignition). Also 
measure the flame signal at low and high firing rates and 
while modulating in between (as applicable). With the 
detector in its final  position, all required  flame  signals 
must be steady (or stable) and as specified in Table 1. If  
you cannot obtain the proper signal, refer to the 
 
Fig. 11. Measuring voltage flame Signal with 7800 SERIES 
controls 
 
Table 1.  Flame signal 
Pilot Turndown Test 
If the detector is used to prove a pilot flame before the main 
fuel valve(s) can be opened, perform a pilot turndown test 
before  welding  the  sight  pipe  into  position.  Follow  the 
procedures in the flame safeguard control instructions and 
in the burner manufacturer instructions. 
Ignition Spark Response Test 
Test to make certain that ignition spark is not actuating the 
flame relay in the flame safeguard control. 
A  Close the pilot and main burner manual shutoff valves. 
B  Start  the  burner  and  run  through  the  ignition period. 
Ignition spark should occur, but the flame LED must not 
light. The flame signal should not be greater than 0.25 
Vdc. 
C  If  the flame relay does  pull in, reposition  the detector  
farther from the spark, or relocate/resight  the  detector 
to  eliminate/reduce  the  detector  response  to  reflected  
UV radiation. It may be necessary to construct a barrier  
to  block  the  ignition  spark  from  the  detector  view. 
Continue  adjustments  until  the  flame  signal  due  to 
ignition  spark  is   less   than  the   flame  signal  values 
Response to other Ultraviolet Radiation Sources 
Some sources of artificial light produce small amounts of 
ultraviolet radiation. Under certain conditions, an ultraviolet 
detector responds  to them as if it is sensing a flame. Do     
not use an artificial light source to check the response of an 
ultraviolet flame detector. To check for proper detector 
operation, conduct flame failure response tests under all 
operating conditions. 
Weld the Sight Pipe 
When the flame signal is acceptable after all adjustments 
are made, remove the detector, and weld the sight pipe in its 
final position (if you are using a swivel mount the pipe may 
already be welded). Then reinstall the detector. 
Final Checkout 
Before  putting  the  burner  into  service,  check  out  the 
installation  using  the    checkout    procedures    in    the  
instructions  for  the  appropriate  flame  safeguard  control. 
After  completing the checkout, run the burner through at  
least one complete cycle to verify correct operation. 
 
CAUTION 
Do  not  put  the  system  into  operation  until  all 
checkout  tests  in  the  instructions  for  the 
appropriate  flame  safeguard  control  and  any 
others  specified  in  the  burner  installation 
instructions are satisfactorily completed. 
 
min. acceptable 
steady signal 
max. acceptable 
steady signal