บริษัท เอดีดี เฟอร์เนส จํากัด 
ADD FURNACE CO.,LTD. 
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170 
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258 
https://www.add-furnace.com E-mail: sales@add-furnace.com 
 
 
 
INSTALLATION 
CAUTION 
1. 
Installer  must  be  a  trained,  experienced  flam 
safeguard control serviceman. 
2. 
Disconnect  power  supply  before  beginning 
installation  to  prevent  electrical  shock  and 
equipment damage. 
3. 
All  wiring  must  comply  with  applicable  local 
electrical codes, ordinances, and regulations. 
4. 
Voltage and frequency of power supply connected 
to  this  detector  must  agree  with      the  values 
marked on the detector. 
6. 
On  multiburner  installation,  each  detector  must 
respond  only  to  the  flame(s)  produced  by  the 
burner it is supervising. 
7. 
Do not connect more than two detectors in parallel 
to a single R7061 or R7861A Dynamic Self-Check 
Ultraviolet amplifier. 
8. 
Perform  all  required  adjustments  and  check-  out 
tests after installation is complete. 
 
Install the Sight Pipe 
After you have determined the location and sighting angle, select 
the sight pipe. A black iron pipe with a diameter of at least 1-1/2 in. 
(38.1  mm)  is  recommended.  Do  not  use  stain-  less  steel  or 
galvanized pipe because they reflect ultraviolet radiation internally 
and complicate aiming the pipe. 
Sight pipes with diameters 2 to 3 in. (51 to 76 mm) produce better 
results  for  horizontal  rotary  burners,  which  require  wide  viewing 
angles.  A  wide  viewing  angle  can  also  be  obtained  by  using  a 
short sight pipe. 
 
Fig. 5. Typical mounting of C7061A/F 
 
Prepare Hole in Wall of Combustion Chamber 
Cut or drill a hole of the proper diameter for the sight pipe   in the 
wall of the combustion chamber at the selected location. 
Flare the hole to leave room for small adjustments of the sighting 
angle. The taper of the hole should be about 1 in. for every 3 in. 
(25 mm for every 76 mm) of Wall thickness. 
 
 
Mount Sight Pipe 
Thread one  end of  the pipe to fit the mounting flange,      union, 
or required coupling. Cut the pipe to the desired length (as short as 
practical)  and  at  an  angle  so  it  fits  flush  with  the  wall  of  the 
combustion  chamber.  Tack-  weld  the  pipe  to  the  wall  in  a  trial 
position.  Do  not  weld  the  sight  pipe  permanently  in  place  until  
after  completing  the  Adjustments and Checkout. 
Install Fittings 
In some cases, the sight pipe does not directly fit the C7061A/F 
mounting flange or union. Also, it may be desirable or necessary 
to  ventilate  the  sight  pipe.  You  may  also  want  to  use  a  swivel 
mount or an antivibration mount. Each of these cases may require 
additional fitting. 
Reducer 
For  sight  pipes  of  larger  diameter  than  the  mounting  flange 
connector or union, install a reducer as illustrated in Fig. 5. The 
reducer will require a close nipple with these external threads: 3/4 
or 1 inch. NPT. 
Sight Pipe Ventilation 
It may be necessary to ventilate the sight pipe to cool the detector 
or  to  clear  a  viewing  path  through  UV  radiation  attenuating 
material. 
For a negative pressure combustion chamber, drilling a few holes 
in the section of the sight pipe outside of the combustion chamber 
will  allow air  at  atmospheric  pressure to  flo  w through  the  sight 
pipe and into the chamber. A perforated pipe nipple between the 
sight pipe and the detector can also be used. 
For a positive pressure combustion chamber, connect a supply of 
pressurized air from the burner blower to flow  through the sight 
pipe and into the chamber. The air pressure must be greater than 
the chamber pressure. 
Swivel Mount (C7061A only) 
To  facilitate  proper flame  sighting,  use  part  no.  118367A  Swivel 
Mount (not supplied). The swivel mount requires a reducer of the 
proper size to mount  it onto the sight pipe.   It also  requires  a 
one-inch  close  nipple  for  mounting  to a C7061 with a one-inch 
connector. (For 118367A Swivel Mount mounting details, refer to 
form 60-0361). 
Antivibration Mount 
The detector withstands normal burner vibration. If the vibration is 
excessive,  part  no.  123539  Antivibration Mount is available. (For 
mounting details, see form 60- 0361). If you use this mount, install 
it before positioning and sighting the detector. 
Mount the Detector 
Mount the detector onto the sight pipe, reducer, or other fit ting. 
The C7061A/F Self-Checking flame detectors incorporate an 
oscillating shutter mechanism and, therefore, require special 
consideration for mounting positions other than vertically sighting 
downward or upward, as illustrated in Fig. 6. The C7061A/F has 
notch and arrow indicators (see Fig. 7 and 9) on the faceplate to 
facilitate mounting    in positions other than those shown in Fig. 7. 
The notch and arrow must be vertically aligned with the notch in the 
up position and the arrow pointing downward (see Fig. 7). The 
C7061A/F must be mounted with the conduit opening located 
approximately 45 degrees below the horizontal