บริษัท เอดีดี เฟอร์เนส จํากัด 
ADD FURNACE CO.,LTD. 
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170 
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258 
https://www.add-furnace.com E-mail: sales@add-furnace.com 
 
 
 
WIRING 
 
  
 
 
CAUTION 
When using a C7061A/F with an R7061 or R7861 
Dynamic  Self-Check  amplifier,  be  careful  not  to 
short  the  white  shutter  lead  wires  together  (by 
wiring incorrectly, leaving an incorrect jumper wire, 
or  stripping the  insulation  too much so the bare    
lead wires can touch). 
If the shutter lead wires are shorted during the 
operation,  the  amplifier  can  be  permanently 
damaged and nonoperative. 
1. 
All wiring must comply with applicable local 
electrical codes, ordinances, and regulations. 
Use NEC class 1 wiring. 
2. 
Keep the flame signal lead wires as short as 
possible  from  the  flame  detector  to    the  
terminal  strip  or  wiring  sub-  base.  
Capacitance increases with lead wire length, 
reducing the signal strength. The maximum 
permissible lead wire length depends on the 
type  of  lead  wire  and  conduit  type  and 
diameter. The ultimate limiting factor in flame 
signal lead wire length is the signal current. 
3. 
The  C7061A/F  detectors  have  a  terminal 
connection block. The wires must be run in a 
conduit. 
4. 
If the lead wires are not long enough to reach 
the terminal strip or wiring subb a s e , make 
the required splices in a junction box. 
5. 
If splicing is necessary, use moisture- 
resistant no. 14 wire suitable for at least 
75°C (167°F) if the detector is used with a 
flam safeguard primary control, or at least 
90°C (194°F)  if used with a flame 
safeguard programming control. 
6. 
For  high  temperature  installations,  use 
Honeywell  specification  no.  R1298020  wire 
or equivalent for  the  F lead wire. This  wire  
is rated up to 204°C (400°F) for continuous 
duty. It is tested for operation up to 600 volts 
and for breakdown up to 7500 volts. For the 
other lead wires,  use  moisture-resistant no. 
14  wire  selected  for  a  temperature  rating 
above the maximum operating temperature. 
7. 
Refer to Fig. 10. for wiring connections 
 
 
 
 
To avoid exceeding the rating of the solid-state shutter 
switch in the R7861 flame signal amplifier, do not connect 
more than two C7061A detectors in parallel. 
IMPORTANT 
Voltage  and  frequency  rating  of  the  C7061A 
must match the power supply of the flame safe- 
guard control. 
 
 
Fig. 10_1. Wiring diagram for C7061A1020 detectors with 
7800 SERIES Flame Safeguard controls with 
shutter drive circuitry. 
 
 
IMPORTANT 
Do not run the flame detector wiring in the same 
conduit  with  high  voltage  ignition  transformer 
wires. 
Connecting Detectors in Parallel 
For a flame that is difficult to sight, using two parallel C7061 
flame detectors reduces nuisance shutdowns. If only one of 
the parallel detectors loses the flame signal, the other 
indicates the presence of the flame and keeps the burner 
running. If two parallel C7061A detectors are  used,  a 
flame simulating failure in either detector causes  the 
burner to shut down. Two C7061A detectors can be 
connected in parallel to the same terminals on 120-volt 
flame safeguard controls. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fig. 10_2. Wiring diagram for C7061A/F detector with 
SLATE, refer to the SLATE Instruction Sheets.