บริษัท เอดีดี เฟอร์เนส จํากัด 
ADD FURNACE CO.,LTD. 
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170 
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258 
https://www.add-furnace.com E-mail: sales@add-furnace.com 
 
 
 
VARIOUS   
TROUBLESHOOTING 
 
CAUTION 
1. 
Be  extremely  careful  while  troubleshooting 
the detector: line voltage is present on some 
of the terminals when power is on. 
2. 
Open the master switch to disconnect power 
before removing or installing the detector or 
its cover. More than one disconnects may be 
involved. 
Equipment Required 
A volt-Ohm meter with a minimum sensitivity of one megohm 
/ Volt and a zero to fi  e or ten Vdc scale is suggested. When 
the  keyboard  display  module  is  available,  a  flame  signal 
displays on the module. For revision of a flame safeguard 
control using the R7061 amplifier, use the W136 or a similar 
test meter. For replacement parts, see specifications section 
UV Sensor Tube Test 
see UV sensor tube test section. 
 
Unsatisfactory Flame Signal 
If a satisfactory flame signal (see  Table  1) cannot be
 
obtained while adjusting the sighting position of the 
detector, follow these procedures. If you encounter other 
problems in the system, refer to the Troubleshooting 
section in the instructions for the appropriate flame 
safeguard control. NOTE: For instructions  for  replacing 
the viewing window, sensing tube, and coil and shutter 
assembly,  see the service section. 
 
Troubleshooting  Procedures
 
First  perform  the  preliminary  inspection.  Then  follow  the 
applicable  procedures  for  either a  low  reading  or  a  zero 
reading  on  the  meter.  After  reinstalling  the  detector  or 
replacing its cover,  recheck the meter reading. To  try to  
obtain  the  proper  flame  signal,  adjust  the  position  of  the 
detector.  If  you  complete  all  of  the  procedures  and  still 
cannot obtain a proper flame signal, replace the detector. 
Preliminary Inspection 
A 
Check for the proper line voltage. Make sure the master 
switch  is  closed,  connections  are  correct,  and  power 
supply is of the correct voltage and frequency. 
 
B 
Check the detector wiring for defects: 
a. 
Incorrect connections. 
b. 
Wrong type or size of wire. 
c. 
Deteriorated wire. 
d. 
Open circuits. 
e. 
Short circuits. 
f. 
Leakage paths caused by moisture, soot, or dirt. 
 
C 
With the burner running, check the temperature at the 
detector. If it exceeds 79°C (175°F): 
a. 
Add additional insulation between the wall of the 
combustion chamber and the detector. 
b. 
Add a shield or screen to reflect radiated heat away 
from the detector, or 
c. 
Add cooling (refer to sight pipe ventilation and 
accessories sections). 
Removing the Detector from the Sight Pipe 
C7061A: 
Loosen  the  three  screws  holding  the  mounting  flange 
together; rotate the detector slightly so the screws clear the 
slots in the back section of the flange; separate the flange; 
and pull off the back section (with the UV Sensor). 
NOTE: The detector will be free as soon as the collar is 
unscrewed; do not drop it. 
C7061F: 
Carefully unscrew from sight pipe 
 
Procedure for a Zero Meter Reading 
A 
Replace the plug-in amplifier. Then recheck the flame 
signal. 
B 
Replace the ultraviolet sensing tube (see Service 
section). Then recheck the flame signal 
C 
Replace the coil and shutter assembly (see Service 
below). Then recheck the flame signal 
D 
If you still cannot obtain a meter reading, replace the 
detector. 
 
IMPORTANT 
At the completion of troubleshooting, be sure to 
perform  the  adjustments  and  checkout 
procedures.