Programmer (Optional) 
46  DC1010/1020/1030/1040 Product Manual  8/05 
Displays  Parameter  Description 
SET 
 
 
Output Limit for Segment 5  Range: 0 to 100% 
If OUT = 0, program will end 
SET 
 
 
Setpoint for Segment 6  Range:  
LSPL (Lower Setpoint Limit) to  
USPL (Upper Setpoint Limit) 
See Table 4-2 for Limit settings 
SET 
 
 
Time Setting for Segment 6  Range: 0-99 hrs:59 minutes 
Ramp segment* = Changing Setpoint time 
Soak segment** = Fixed Setpoint time 
SET 
 
 
Output Limit for Segment 6  Range: 0 to 100% 
If OUT = 0, program will end 
SET 
 
 
Setpoint for Segment 7  Range:  
LSPL (Lower Setpoint Limit) to  
USPL (Upper Setpoint Limit) 
See Table 4-2 for Limit settings 
SET 
 
 
Time Setting for Segment 7  Range: 0-99 hrs:59 minutes 
Ramp segment* = Changing Setpoint time 
Soak segment** = Fixed Setpoint time 
SET 
 
 
Output Limit for Segment 7  Range: 0 to 100% 
If OUT = 0, program will end 
SET 
 
 
Setpoint for Segment 8  Range:  
LSPL (Lower Setpoint Limit) to  
USPL (Upper Setpoint Limit) 
See Table 4-2 for Limit settings 
SET 
 
 
Time Setting for Segment 8  Range: 0-99 hrs:59 minutes 
Ramp segment* = Changing Setpoint time 
Soak segment** = Fixed Setpoint time 
SET 
 
 
Output Limit for Segment 8  Range: 0 to 100% 
If OUT = 0, program will end 
Back to “Operation” Mode – See Table 3-3 
*A Ramp Segment is the time it will take to change the setpoint to the next setpoint 
value in the program. 
** A 
Soak Segment is a combination of soak setpoint (value) and a soak duration 
(time).