- Observe proper polarity. 
- If not using the integrated EOL resistors, set all switches to 
OFF. 
- If using the integrated EOL resistors: 
1. Connect the sensor to the panel (see wiring diagrams 
below). 
2. Set the appropriate tamper [RT], alarm [RA] and trouble [RF] 
DIP switches to ON (see Step 4 on page 2). 
Notes: 
-  Consult the Control Panel manual to determine 
proper EOL selection. 
-  The Alarm, Tamper and Trouble EOL settings must 
each only have one switch ON. 
-  The EOL values should be set at the same time. 
 
Wiring Examples 
Alarm, Tamper and 
Trouble configured 
to one loop. 
 
   
Alarm, Tamper and 
Trouble configured 
to two loops. 
 
   
 
 
 
 
 
 
 
 
 
 
 
 
1.  Close the sensor and apply power to the sensor. Initialization is  
complete when the LED stops flashing slowly (about 30 seconds). 
2.  Walk through the detection area and observe the LED. 
3.  Adjust the microwave range as necessary to meet installation requirements. 
Walk test mode is active for 10 minutes, then automatically exits test mode, 
disables the LED and enters normal operation mode. For an additional 10 
minute walk test, enable walk test mode again with the flashlight feature (see the 
following page). 
RF = Trouble EOL resistor 
W1 = 1 and 2 loop connection resistor. 
-  During power up and walk test 
modes the LED is active 
regardless of the LED 
Enable/Disable DIP switch setting. 
-  When the microwave sensitivity is 
set to minimum, the sensor range 
is reduced to 5m.
  
LED  Power Up 
Microwave 
OFF  OFF 
Green  OFF 
ON  
PIR 
OFF  OFF