Extinguishing Control Computer 8010 - Series 2
110 FB 798352 / 11.07
19 Specifications
Main voltage : 230 V AC
Rated frequency : 50 Hz
Rated current : 0.7 A
Battery capacity : 2 x 12 V / 24 Ah
Battery charging voltage : 13.65 V DC @ 25 °C
Ambient conditions : class 3k5 in accordance to DIN EN 60721-3-3
Ambient temperature : -5 °C to +45 °C
Storage temperature : -10 °C to +50 °C
Protection class : I in accordance with DIN EN 60950-1
Protection rating : IP 30
Housing : Sheet steel with swivel-mounted front door
Colour : Light grey, similar RAL 7035 / blue, similar RAL 5003
Weight : approx. 18.3 kg (without rechargeable battery)
Dimensions (W x H x D): : 488 x 625 x 210 (mm)
VdS approval : G 200090
CE certificate : 0786-CPD-20223
Alarm zone inputs 1 to 8 : Monitored differential alarm zone for connecting automatic fire detectors.
End-of-line resistor (10kΩ normal / 1kΩ alarm)
Technical zones : Monitored differential alarm zone for connecting
Manual Call Points (MCP) series 9000 or dry contacts.
End-of-line resistor (10kΩ normal / 1kΩ alarm)
Relay contacts
Relays No. 1 to 8 : Changeover contacts, max. 30 V DC / 2 A
Operating mode potential-free or positive-switching / monitoring can be
set via plug-in jumpers
Relays No. 9 to 11 : Changeover contacts, max. 30 V DC / 2 A
Programmable, relays 10 and 11 with selectable function for
>Emergency Operation Trouble< and >Emergency Operation Fire<
Relays No. 12 and 13 : Dry contact (NO), max. 230 V AC / 2 A,
suitable for switching AC mains voltage