80 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Programming Master Programming Level
MNS Override
Pressing 3 while viewing System Setup Screen #3 will allow the programmer to configure the system for
use with the Mass Notification System (ECC-50/100 panel). Each press of the 3 key will toggle the display
between MNS Override No and MNS Override Yes. When MNS Override No is selected, the ECC-50/100
panel does not have permission to override the FACP. When MNS Override Yes is selected, the ECC-50/100
panel will override the FACP, taking control of its NACs and control modules during a mass notification
event. Refer to the ECC-50/100 Manual for more information. When the Canadian Option is set to On, the
MNS Override feature will become unavailable.
Auxiliary Power
Two Special Application 24 VDC power outputs are available at TB11 on the main circuit board. Pressing 3
while viewing System Setup Screen #4 displays the following:
Select the desired output. The following screen will be displayed.
Each output can be programmed as resettable or non-resettable power. Non-resettable power is suitable for powering annunciators while
resettable power is suitable for powering smoke detectors. Each press of the 2 key will cause the display to toggle between Resettable
Yes and Resettable No.
In addition, Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press 1. Each press of the 1 key will cause
the display to toggle between Class A Yes and Class A No.
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and
troubles, after the panel has been silenced. Refer to “Trouble Reminder” on page 71, for a detailed descrip-
tion of this feature. Pressing 2 while viewing System Setup Screen #4 will cause the display to toggle to
Trouble Rem 4 or Trouble Rem 24, which enables this feature for resound at either 4 or 24 hours, respec-
tively. Each press of the 1 key will cause the display to toggle between Trouble Rem 4 or Trouble Rem 24.
Refer to the table on page 49 for permissible settings.
Language
The language option is used to change the text on the panel display to either English or French. Pressing the
3 key will cause the display to offer a choice of 1=English and 2=French.
Charger Enable
If using an external battery charger, the FACP battery charger must first be disabled. Pressing 1 while view-
ing System Setup Screen #5 will cause the display to toggle to Charger Enab No, which will allow the use
of an external battery charger. Each press of the 1 key will cause the display to toggle between Charger
Enab Yes and Charger Enab No.
4XTMF Supervision
If a 4XTMF Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing 2 while viewing System Setup Screen #5 will cause the display to toggle to 4XTM Supv Enab. Yes,
which means there is a 4XTMF installed. Each press of the 1 key will cause the display to toggle between
4XTM Supv Enab. No and 4XTM Supv Enab. Yes. Refer to the table on page 49 for permissible settings.
Remote Sync Enable
Synchronization is a feature that controls the activation of notification appliances in such a way that all
devices will turn on and off at exactly the same time. Refer to Section 2.5, “Remote Synchronization Out-
put”, on page 28 for more information. To enable remote synchronization, press the 3 key while viewing
System Setup Screen #5. Each press of the key will toggle the screen between Rem Sync Enab Yes and Rem
Sync Enab No.
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE NO
System Setup Screen #3
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
System Setup Screen #4
AUX 1
1=CLASS A YES
2=RESETTABLE YES
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
System Setup Screen #4
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5