Galaxy Programming Manual
140
Option 62 – Full Test (Galaxy 18, 60, 128, 500, 504 & 512)
The Full Test option allows two zones to be selected and tested under full set conditions. Activating the
selected zone results in a full alarm condition, including remote signalling. Constantly active zones (Security,
24 Hours, PA, Fire) remain active throughout the Full Test; an activation generates the appropriate local or
full alarm depending on the zone.
On selecting the Full Test option, the address and function of the first zone on the system is displayed. Move
to the required zone by pressing the A or B keys or by entering the zone address. Press the ent key. An
option is then given to choose a second confirm zone. If you press the A (YES) key, select a second required
zone by pressing the ent key. If you press the B (NO) key, the system begins the full setting procedure.
Activating the zone results in a full alarm condition. To end the full test unset the system.