Option 63 – Options (Galaxy 18, 60, 128, 500, 504 & 512)
The Options function allows the Galaxy to be divided into group subsystems and also allows the MAX
proximity access control readers to be integrated into the system.
Table 25. Groups/Max Modules per Panel
63 - Options
lenaPpuorGxaM
8G02
81G33
06G44
821G88
005G6161
405G2323
215G2323
Options
1 = Groups
1 = Group Mode
0 = Disabled
1 = Enabled
2 = Setting Logic
A/B to move to group and ent to select.
Number keys to toggle:
= status of group uninportant
S = Group must be set to allow group to set.
3 = Group Name
A/B to move to group and ent to select.
# = toggle upper case, lower case or library text.
= delete last character.
A/B = move to character/word.
ent = assign character/word.
esc = save programming.
2 = MAX
1 = MAX Mode
0 = Disabled
1 = Enabled
2 = MAX Address
A/B to select line (G500, G504 & G512)
ent to start MAX search.
0 = On-line, ent then key 0 - 7 to readdress MAX.
1 = Standalone
3 = MAX Parameters
A/B to move to required MAX address.
# to display MAX address graphic.
ent to select.
1 = Descriptor# = toggle upper case, lower case or library text.
= delete last character
A/B = move to character/word
ent = assign character/word
esc = save programming
2 = Relay Duration
1 - 60 seconds (default = 05).
3 = Open Timeout
0 - 60 seconds (default = 10).
4 = Groups
Press group number to toggle group on/off
(G504 & 512) A/B to move between group blocks.
5 = Emergencies
Enable or disable option. If group mode is enabled,
a separate enable is available for each group.
6 = AntiPassBack
1 = Mode
3 = Forgive
0 = Off
No antipassback restriction.
1 = Soft
Access is never denied but any violations
will be recorded in the event log.
No access will be granted for a second
2 = Hard
swipe within the antipassback period
following a valid swipe.
2 = Timout
(0 - 60 minutes). Specifies the time that the
antipassback restrictions last for.
Allows the engineer to remove all antipassback
restrictions for the selected MAX. Use the
A>B< keys to select the reader address then
press enter to forgive.