Galaxy Flex Installer Manual Parameters [51]
77
System Text [51.15]
Use this option to assign two text strings to the system: press 1 to select the System ID or 2
to select the Panel Location.
1=System ID 16 character identification of the system. Use this when connecting to
Remote Servicing software.
2=Panel Location 16 character message of where control is fitted.
Text is written using the alpha-numeric assembly method:
 erases characters.
# selects upper case, lower case or library.
A B scrolls through the alphabet of character/words.
000–500 selects alphabet character or words directly.
ent positions selected characters/words.
esc accepts the programming and returns to the previous level.
Soak Time [51.16]
Use this option to set the number of days that zones can be soak tested for. The default is 7
days and the range is 1 to 14 days.
Note: Change default settings before programming in Soak [55].
Restart [51.17.1]
Use this option to re-configure the system without the need to remove and reconnect the
power. The system displays WARNING!!! ent=RESET SYSTEM.
Press ent to reconfigure the system. The keypad display becomes blank for a few seconds,
then displays the message Configuring Please Wait. When configuration is complete the
banner returns to the normal display (day mode). The Restart option configures any modules
that have been added to the system but gives an alarm if there are any tampers open or if any
modules are reported as missing.
Notes:
1. This parameter exits engineer mode. It is however recommended that the exit engineer
mode sequence is used when adding or removing modules from the system.
2. Outputs are momentarily reset during the restart. If the system has a communications
requirement, put it on test before using the restart.
Defaults [51.17.2]
Use this option to select the panel default settings for a particular country.
The system displays WARNING!!! ent=RESET SYSTEM.
Press
ent to reconfigure the system.

Table of Contents

Other manuals for Honeywell Galaxy Flex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Flex and is the answer not in the manual?

Honeywell Galaxy Flex Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy Flex
CategoryControl Panel
LanguageEnglish

Related product manuals