Section 5: Programmer Keyboard Commands
5-5
System Status Displays – continued
Battery Charger
OK
Battery Charger
Indicates the battery charger circuit status (
either OK
or NOT OK).
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Line Voltage
xx.xxV
Line Voltage Display
The line voltage [this value is the peak voltage from the
power transformer or RMS x 1.414] of the
communicator can be viewed on the 7720P. An asterisk
(*) next to the voltage indicates that this is below the
accepted level.
Press the [Space] key to go back to the System Status
Display. Press the backspace [BS] key to go to the
previous field.
[T]
Test Msg Sent
Test Alarm
Sends a Test alarm to AlarmNet. Functional for a
registered communicator only. If the device is not
registered, a message is displayed indicating that the
command cannot be executed.
NOTE: If two CSIP’s are used, test alarms are sent to
each central station. In addition, if the primary fails to
report, a second (backup) message is sent to the
secondary station.
[X]
Reset CPU Y/N
Reset the communicator.
Pressing [N] returns to normal mode.
Pressing [Y] resets the device.
[
]
(UP arrow)
Registering …
Registration
Registers a programmed communicator with AlarmNet.
[
]
(DN arrow)
Enter PIN#
Registration with PIN for Replacement
Registers a replacement communicator with AlarmNet,
once programmed, using the existing PIN #.
[0]
Force Server Update?
Y/N
Force Upload of Configuration File to Server
Pressing [Y] will force the device to upload its entire
configuration file to the server.
Pressing [N] cancels the operation.
NOTE: If the GSM communicator is not initialized
when you enter this command, the following screen will
be displayed:
Cannot Upload
Try Later! _
Wait for the RSSI LEDs to light, indicating the GSM
communicator has completed its initialization, and try
again.
[ENTER]
Strt Prog Mode?
Y/N_
Enter Program Mode
Press [Y] to enter program mode; otherwise, press [N].