Decommissioning,storage,renewedstart‐up,disposal
UsermanualforHONR100gaspressureregulatorwithHONP095NGpilot 79
Observethefollowingrules:
Alldeviceopeningsandfittingsmustbesealedandprotectedfromsoilinganddamage.
Thedevice’smaintenanceconditionmustbeindicatedwithalabel:
Datewhenmaintenancewaslastperformed
Operatingtimesandoperationcyclessincethelasttimemaintenancewas
performed
Donotstorethedeviceoutdoors.
Storethedeviceinadryanddust‐freeenvironmentonaflatsurface.
Donotexposethedevicetoanyaggressivemedia,ozoneorionizingradiationortodi‐
rectheatsources.
Storageconditions:
Temperature:0 °Cto25 °C(32 °Fto77 °F)
Relativehumidity:< 55%.
Avoidmechanicalvibrations.
Storageperiods:Checkthedevicefordamageandsoilingatleastannually.Whenit
comestomaintenancecycles,taketheprecedingoperatingtimeintoaccountinaddi‐
tiontothestoragetime.
9.3 Puttingthegaspressureregulatorbackintooperation
Riskofinjuryposedbyburstingpartsintheeventthattheyaresubjectedtopressurein
thewrongdirection
Thedevicehasbeendesignedforaspecificdirectionofflow,whichislabeledonthedevice.
Subjectingthedevicetopressureinthewrongdirectionmayresultinseriousinjurycaused
byburstingparts.
Pressurizethesystemonlyontheinletside.
Thisprocedurecanbeusedifthepilot’srequiredsetpointsareknown,theywerealreadyset
duringearliercommissioning,andredoingoradjustingthesettingsisoutofthequestion.
Afterbeinginadepressurizedstate,theadjustmentprocessforthegaspressureregulator
willberelativelysluggish.Duringcommissioning,alwaysmakesuretowaitbetweenthe
individualstepsuntilthedesiredstateisreached.
Thenumbershavethefollowingmeaning:
Storingdevicesthathave
alreadybeeninoperation
andthatareintendedto
beputbackintoopera‐
tionlateron
Pressurizedparts
Puttingthevalveback
intooperation
Basicpointers
Gasregulatinglinecom‐
ponents